COMPONENTS TESTING

COMPONENTS TESTING

TESTING THE ELECTRONIC CONTROL BOARDS FOR XQ MODELS

X Star

PM

Power

ERROR CODE LISTINGS Cool

Fan

Speed Mode MoneySaver®

 

 

Fan Only

 

 

Clock

Timer

Set

Start Time

On/Off

Hour

 

ERROR CODE LISTINGS

E1 SHORT CYCLE SITUATION: Defi ned as (compressor powered on before the three minute time delay ten times in one hour. Investigate and correct short cycling problem.

E2 KEYBOARD STUCK ERROR: If key button(s) are pressed continuously for twenty seconds or more. If MODE key is stuck, unit will default to cool. Exit Error Code Mode to see if error “E2” is no longer displayed and unit is functioning. Replace board if “E2” still displays after exiting Error Code Mode.

E3 FROST PROBE OPEN: Normal operation is allowed.

Stop Time

Activating Test Mode:

Temp/Hour

Ohm frost probe. Replace probe if ohm value not read. If ohm value is present replace board.

E4 FROST PROBE SHORT: Normal operation allowed.

Activate test mode by pressing at the same time the “MODE” button and the “TEMP Activating Test Mode:button on XQ models. LEDs for Hour, Start, and Stop will blink 1 bps while Test Mode is active.

Test Mode has duration of 90 minutes. Test Mode can be activated under any conditions, including Off. Test Mode is cancelled by pressing the On/Off button, unplugging the unit, or when the 90 minutes is timed out. All settings revert to the factory default settings of Cool, 75 degrees F, Timer and Set Hour features are nonfunctional.

Test Mode overrides the three-minute lockout, all delays for compressor and fan motor start / speed change, and no delay when switching modes.

During Test Mode, the default settings are; Unit ON, Money Saver ON, 60°F, and High fan speed.

Activating Error Code Mode: (Submode of Test Mode) Unit must be in Test Mode to enter Error Code Mode

1.Activate Error Code Mode by pressing the “TIMER ON/ OFF” button on XQ models. LED for the “TIMER ON/OFF” will fl ash 1 bps while Error Code Mode is active. Pressing the “TEMP/HR Manual backgroundbutton will display 00. Consecutive presses will scroll through all error codes logged. Press

the “TEMP/HR Manual backgroundbutton to see the reverse order of all error codes logged. When the end of logged error codes is reached the temperature set point will appear.

IMPORTANT: Error Codes are cleared from the log by exiting from Error Code Mode. To exit on XQ models, press Timer On/Off button. Or unplug unit to exit Error Code Mode. Plug unit in after 5 seconds to resume normal operation of unit.

Replace probe.

E5 INDOOR PROBE OPEN: Control assumes indoor ambient temperature is 90 degree F and unit will operate. Ohm indoor probe. Replace probe if ohm value not read.

E6 INDOOR PROBE SHORT: Control assumes ambient temperature is 90 degree F and unit will operate. Replace probe.

NOTE: All Error Code displays for Frost & Indoor Probe will allow unit to operate. Unit may or will ice up if faulty components not replaced.

FROST PROBE SENSOR: disables compressor at 35 degrees F.

INDOOR PROBE SENSOR: Control range is 60°F to 90°F +/- 2°F.

Indoor temperature will be displayed by pressing: (XQ units) The Fan Speed button and the “TEMPManual backgroundbutton.

The indoor temperature will be displayed for 10 seconds. The display will change back to the Set Point temperature by pressing any key button except for the On/Off button. The indoor temperature can be viewed in all modes, including test mode.