![External Static Pressure](/images/new-backgrounds/33085/3308543x1.webp)
External Static Pressure
External Static Pressure can best be defined as the pressure difference (drop) between the Positive Pressure (discharge) and the Negative Pressure (intake) sides of the blower. External Static Pressure is developed by the blower as a result of resistance to airflow (Friction) in the air distribution system EXTERNAL to the
Resistance applied externally to the
External Static Pressure is affected by two (2) factors.
1.Resistance to Airflow as already explained.
2.Blower Speed. Changing to a higher or lower blower speed will raise or lower the External Static Pressure accordingly.
Theseaffectsmustbeunderstoodandtakenintoconsideration when checking External Static Pressure/Airflow to insure that the system is operating within design conditions.
Operating a system with insufficient or excessive airflow can cause a variety of different operating problems. Among these are reduced capacity, freezing evaporator coils, premature compressor and/or heating component failures. etc.
System airflow should always be verified upon completion of a new installation, or before a
1.Set up to measure external static pressure at the supply and return air.
2.Ensure the coil and filter are clean, and that all the registers are open.
3.Determine the external static pressure with the blower operating.
4.Refer to the Air Flow Data for your
5.If the actual airflow is either too high or too low, the blower speed will need to be changed to appropriate setting or the ductwork will need to be reassessed and corrections made as required.
6.Select a speed, which most closely provides the required airflow for the system.
7.Recheck the external static pressure with the new speed. External static pressure (and actual airflow) will have changed to a higher or lower value depending upon speed selected. Recheck the actual airflow (at this "new" static pressure) to confirm speed selection.
8.Repeat steps 8 and 9 (if necessary) until proper airflow has been obtained.
EXAMPLE: Airflow requirements are calculated as follows: (Having a wet coil creates additional resistance to airflow. This addit ional resistance must be taken into consideration to obtain accurate airflow information.
Checking External Static Pressure
The airflow through the unit can be determined by measuring the external static pressure of the system, and consulting the blower performance data for the specific
Determining the Indoor CFM: Chart A – CFM
|
|
| MODEL |
|
| |
|
|
|
|
|
|
|
| VEA09/VHA09 | VEA12/VHA12 | VEA18/VHA18 | |||
ESP (") | Low | High | Low | High | Low | High |
.00" | 340 | 385 | 420 | 470 | 430 | 480 |
.10" | 300 | 340 | 350 * | 420 ** | 400 | 450 |
.20" | 230 | 280 | 290 | 350 | 340 | 400 |
.30” | 140 | 190 | 250 | 300 | 290 | 330 |
Highlighted values indicate rated performance point. Rated performance for
*VEA12
Rated Performance for
**VHA12
|
| Model | |
| VEA24/VHA24 | ||
ESP (") | Low |
| High |
.00" | 690 |
| 740 |
.10" | 610 |
| 700 |
.20" | 560 |
| 640 |
.30" | 510 |
| 580 |
.40" | 450 |
| 520 |
Highlighted values indicate rated performance point.
21