ELECTRICAL REQUIREMENTS

ELECTRICAL REQUIREMENTS

ELECTRIC SHOCK HAZARDWARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before service or instal- lation. All electrical connnections and wiring MUST be installed by a qualified electrician and conform to the National Electrical Code and all local codes which have jurisdiction. Failure to do so can result in personal injury and/or death.

NOTICE

Not following the previous WARNING could result in fire or electrically unsafe conditions which could cause moderate or serious property damage. Read, understand and follow the previous warning.

Wire Size

“Use ONLY time delayed fused disconnect or HACR type circuit breaker as indicated on the unit’s rating plate. Proper current protection to the unit is the responsibility of the owner”.

Unit MUST

All 208/230v chassis must be hard wired with properly sized breaker. See nameplate for specific chassis electrical requirements. See below for unit wiring. For wall thermostat wiring, see page 12. Use HACR type breakers to avoid nuisance trips. All field wiring must be done in accordance with NEC and local codes.

Supply voltage

Supply voltage to the unit should be a nominal 208/230 volts. It must be between 197 volts and 253 volts. Supply voltage to the unit should be checked WITH THE UNIT IN OPERATION. Voltage readings outside the specified range can be expected to cause operating problems. Their cause MUST be investigated and corrected.

For VPAK Cool with Electric Heat 9-18K

ELECTRICAL DATA

 

 

VEA09K

 

 

VEA12K

 

 

VEA18K

 

 

 

 

 

 

 

 

Heater Watts

2500/2050

3400/2780

5000/4090

2500/2050

3400/2780

5000/4090

2500/2050

3400/2780

5000/4090

Voltage

 

230/208

 

 

230/208

 

 

230/208

 

Heating BTU/h

8500/7000

11600/9500

17000/13900

8500/7000

11600/9500

17000/13900

8500/7000

11600/9500

17000/13900

Heating Current (Amps)

10.9/9.9

14.8/13.4

21.7/19.7

10.9/9.9

14.8/13.4

21.7/19.7

10.9/9.9

14.8/13.4

21.7/19.7

Minimum Circuit Ampacity

15

19.9

28.6

15

19.9

28.6

15

19.9

28.6

Branch Circuit Fuse (Amps)

15

20

30

15

20

30

15

20

30

LRA - Compressor (Amps)

22

22

22

30

30

30

42

42

42

Cooling Current (Amps)

4.2/4.4

4.2/4.4

4.2/4.4

5.2/5.4

5.2/5.4

5.2/5.4

8.1/8.6

8.1/8.6

8.1/8.6

Basic heater Size

2.5 Kw

3.4 Kw

5.0 Kw

2.5 Kw

3.4 Kw

5.0 Kw

2.5 Kw

3.4 Kw

5.0 Kw

Power Connection

 

HARD WIRED

 

 

HARD WIRED

 

 

HARD WIRED

 

 

 

 

 

 

 

 

 

 

 

Recommended Branch

 

 

 

 

 

 

 

 

 

Circuit Wire Sizes **

14

12

10

14

12

10

14

12

10

* AWG-American Wire Gauge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For VPAK Heat Pumps 9-18K

ELECTRICAL DATA

 

 

VHA09K

 

 

VHA12K

 

 

VHA18K

 

Heater Watts

2500/2050

3400/2780

5000/4090

2500/2050

3400/2780

5000/4090

2500/2050

3400/2780

5000/4090

Voltage

 

230/208

 

 

230/208

 

 

208/230

 

Heating BTU/h

8500/7000

11600/9500

17000/13900

8500/7000

11600/9500

17000/13900

8500/7000

11600/9500

17000/13900

Heating Current (Amps)

10.9/9.9

14.8/13.4

21.7/19.7

10.9/9.9

14.8/13.4

21.7/19.7

10.9/9.9

14.8/13.4

21.7/19.7

Minimum Circuit Ampacity

15

19.9

28.6

15

19.9

28.6

15

19.9

28.6

Branch Circuit Fuse (Amps)

15

20

30

15

20

30

15

20

30

LRA - Compressor (Amps)

18.5

18.5

18.5

26

26

26

42

42

42

Cooling Current (Amps)

4.1/4.3

4.1/4.3

4.1/4.3

5.3/5.5

5.3/5.5

5.3/5.5

8.2/8.6

8.2/8.6

8.2/8.6

Basic heater Size

2.5 Kw

3.4 Kw

5.0 Kw

2.5 Kw

3.4 Kw

5.0 Kw

2.5 Kw

3.4 Kw

5.0 Kw

Power Connection

 

HARD WIRED

 

 

HARD WIRED

 

 

HARD WIRED

 

 

 

 

 

 

 

 

 

 

 

Recommended Branch

 

 

 

 

 

 

 

 

 

Circuit Wire Sizes

14

12

10

14

12

10

14

12

10

* AWG-American Wire Gauge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

Page 7
Image 7