ELECTRICAL TROUBLESHOOTING CHART - COOLING

24K BTU

NO COOLING OPERATION

Compressor and outdoor fan motor run but indoor blower does not run

Yes

Indoor blower runs but outdoor fan motor and compressor do not run

Yes

Insure that Fuses

are good and/or that Circuit Breakers are

on and voltage is 208/230

O.K.

 

 

Set thermostat to

 

 

 

"Cool," move the Temp.

 

 

 

lever below the present

 

 

 

Room Temp.

 

 

 

 

 

 

 

 

 

 

O.K.

 

 

 

 

 

 

 

 

 

Compressor outdoor

 

 

 

 

fan motor and indoor

 

 

 

 

 

 

No

blower should now

 

 

 

 

operate

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

See Refrigerant Circuit

 

 

 

diagnosis if unit still is

 

 

 

not cooling properly

 

 

 

 

 

 

 

Before continuing

check for Error

Codes, see

electronics control

diagnostics on

page 16

Nothing operates, entire system appears dead

 

 

 

No

Yes

 

 

 

Line voltage present at the Transformer Primary

Yes

24 Volts at

“R” Terminal on board

Yes

24 Volts present at Y terminals on t-stat and board?

Yes

No

No

No

Check Supply Circuit’s jumper at transformer. If okay, replace board

Problems indicated with

Control Transformer replace board

Problems indicated with Room Thermostat or Control Wiring. Fix.

24V at t-stat and

control wiring?

Yes

Is Line Voltage present at Motor Leads?

Yes

Check Capacitor, is Capacitor Good?

Yes

Motor should run

No

No

No

No

Defective t-stat

defective control wiring

or transformer

Problems indicated

in Blower Relay of board

Replace Capacitor

Possible motor problem indicated. Check motor thoroughly

Supply Circuit problems, loose Connections, or bad Relays/Board

Replace Capacitor

and/or Start Assist

Device

3 minute delay done

 

 

 

 

 

 

 

on control board?

No

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

208/230 Volts present

 

 

 

at compressor’s relay

 

 

 

No

 

on control board?

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

Is compressor/fan

 

 

 

 

motor contactor

 

 

 

 

No

 

 

closed?

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

Are wiring,

 

 

 

 

connections, and

 

 

 

 

No

 

 

capacitor good?

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is Locked Rotor

 

 

Voltage a minimum of

 

 

 

No

197 Volts?

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

Are Capacitor and (if

 

 

so equipped) Start

 

 

 

No

Assist good?

 

 

 

 

Wait until done

Replace control board

Replace contactor

Repair or replace

component

Compressor and outdoor fan motor should now operate

Yes

See Refrigerant

Circuit Diagnosis

if unit still is not

cooling properly

 

 

 

 

Yes

 

 

 

 

 

 

Allow ample time

 

Have System

 

for pressures to

No

Pressures Equalized?

 

equalize

 

 

 

 

Yes

 

 

 

 

 

 

Possible Compressor

 

 

 

 

 

 

 

 

problem indicated.

 

Compressor should

 

 

 

See Compressor

No

run

 

Checks

 

 

 

37