Friedrich R410A Compressor Heat Heat / Cool Units, Heat Mode in Cool with Electric Heat Units

Models: R410A

1 61
Download 61 pages 11.89 Kb
Page 11
Image 11
(Compressor Heat)

Note: Unit is operated by a wired remote wall t-stat which is connected to an electronic control board at the VPAK unit.

Heat Mode in Cool with Electric Heat UnitsHeat Pump With Electric Heat Operation(Compressor Heat)

Condition 1Manual backgroundManual backgroundHeat / Cool Units

Manual backgroundManual background The Manual backgroundManual background

set point of the t-statManual background if Manual backgroundManual background

Heat Mode in Cool with Electric Heat Units

When the t-stat is in the Heat Mode, if the indoor ambient temperature is below the heat set point, the fan turns on 5 seconds prior then the electric heat will turn on. When the t-stat is satisfied, the electric heat will turn off. The fan turns off 15 seconds later.

Heat Pump With Electric Heat Operation

This heating has two heating methods. If the ambient indoor temperature is below the heat set point and the compressor is not locked out, the compressor turns on. If the ambient temperature rises above the t-stat’s heat set point, the compressor turns off.

If the Compressor is Locked Out on the 3 Minute Time Delay and Electric Heat is Available

1.The control turns on the electric heat until the compressor is not locked out.

2.After lockout, the control turns off the electric heat, waits 5 seconds, then turns on the compressor. (The wired remote wall t-stat’s time delay may override this feature).

Condition 1

Manual background Thereafter, the unit will switch back to Heat Pump heat until the outdoor coil temperature sensor rises to 45Manual background or greater.

10

Page 11
Image 11
Friedrich R410A manual Compressor Heat Heat / Cool Units, Heat Mode in Cool with Electric Heat Units, Condition