Friedrich SQ10N10, SQ08N10, SQ05N10, SQ06N10, EQ08N11 manual Error Codes, Key Sequence, Action

Models: EQ08N11 SQ06N10 SQ05N10 SQ08N10 SQ10N10

1 67
Download 67 pages 59.79 Kb
Page 45
Image 45
ERROR CODES

ERROR CODES

Error

Problem

Control Board's Action

Code

 

 

1

Front Panel Button Stuck For More

Continue to monitor for "OPEN" (Unstuck) switch. Do not process switch

Than 20 Seconds

input.

 

2Input Voltage Out of Specification (103 Open all relays until voltage is back within specs. Resume operation - 127 / 187 - 253)

3Indoor Temperature Sensor is Open or Set temp to 75°F in COOLING or 68°F in HEATING. Unit continues to

Shortedoperate

4

Indoor Coil Temperature Sensor is

Control Board sets temp to a default of 40°F. Override sensor. Unit

Open or Shorted

continues to operate.

 

5

Outdoor Coil Temperature Sensor is

Sets temp to 20°F. Override sensor. Continue operation. Use Elec Heat if

available for HEATING. If not available use HEAT PUMP if outdoor temp

Open or Shorted

 

allows.

 

 

 

 

Shut down for 5 min. Resume operation for 3 min. Continues to monitor. If

6Outdoor Coil > (grater than) 175 F test fails 3 times, the unit operation is locked out. Unplug and replug to reset.

7Indoor Coil < (less than) 30 F for 2 Turn compressor off. Run High Fan speed. When coil temp reachs 45°F

consecutive minutesresume operation after lockout time.

8Unit Cycles > (grater than) 9 Times per Continue operation. Continue to monitor. Take no action. Log Only. hour

9

Unit Cycles < (less than) 3 Times per

Continue operation. Continue to monitor. Take no action. Log Only.

Hour

 

 

 

 

Only used if Electric Heat is available. Run High Speed and Electric heat

10

Room Freeze Protection

until room temp reaches 46°F. Display "FRZ" during operation. Logged

 

 

Only

11

WallStat Problem or Connection Issue

Unit operates based on standard t-stat connection. If miswired, unit will not

not operate. (See pages 32 and 68)

12

Not Applicable

Not Applicable

 

 

 

13

Not Applicable

Not Applicable

 

 

 

14

Discharge Air Temperature Sensor is

Override Sensor. Set temp to 75°F. Continue to monitor. Set error code 14

Open or Shorted

ON.

 

15

Not Applicable

Not Applicable

16Temperature Beyond Operating Limits Ambient temp < (less than) 0°F and ambient temp > (greater than) 130°F. Set error code 16 ON. When cleared return unit to normal.

17

Equipment Doesn't Meet Minimum

Must have compressor enabled and at least 2 fan speeds

Configuration

 

 

18

Not Applicable

Not Applicable

 

 

 

19

Not Applicable

Not Applicable

20

Not Applicable

Not Applicable

 

 

 

21

Not Applicable

Not Applicable

22

Outdoor Coil Temperature < 30 F for 2

Unit will use electric heat to satisfy heating demands until temp is greater

consecutive Minutes

than 45°F. Unit must be a Heat Pump with electric heat.

 

23

Not Applicable

Not Applicable

24

Not Applicable

Not Applicable

 

 

Key Sequence

 

 

Action

 

To Access Error Codes

Press the fan speed and key for 3 seconds

 

Reset Error Codes & Error History

Press + timer/schedule for 3 seconds

 

When you have entered the Error Codes section, an “E” will appear. Use the up

and down keys to scroll through error codes.

Only active error codes will display.

 

 

 

44

Page 45
Image 45
Friedrich SQ10N10, SQ08N10, SQ05N10, SQ06N10, EQ08N11 manual Error Codes, Key Sequence, Action