Frymaster 824E, Combinations, 2424E operation manual Danger

Models: 2424E 824E Combinations

1 30
Download 30 pages 14.58 Kb
Page 10
Image 10
Manual background

When the fryer is leveled in its final position, install the restraints provided with the unit to limit its movement so that it does not depend on or transmit stress to the electrical conduit or connection. Install the restraints in accordance with the provided instructions (see illustration below). If the restraints are disconnected for service or other reasons, they must be reconnected before the fryer is used.

Manual background DANGER

Single fryers may tip and cause personal injury if not secured in a stationary position.

5.If the fryer is equipped with a power cord, plug the cord securely into a properly grounded outlet of appropriate voltage for the specific fryer configuration.

If the fryer is not equipped with a power cord, connect a power cord appropriate for the voltage rating of the fryer in accordance with the field connection diagrams that follow. Refer to the table on the following page to determine the appropriate wire gauge.

Manual background DANGER

Copper wire suitable for at least 167°F (75°C) must be used for power connections.

VOLTAGE

PHASE

WIRE

MINIMUM SIZE

AMPS

SERVICE

AWG

 

(mm2)

(PER LEG)

208

1

3

6

 

16

31

208

3

3

6

16

18

240

1

3

6

16

27

240

3

3

6

16

16

480

1

3

8

16

14

480

3

3

8

10

8

2-3

Page 10
Image 10
Frymaster 824E, Combinations, 2424E operation manual Danger