CHAPTER 4: Troubleshooting

Thermal alarm

Symptom

Cause

Action

 

 

 

 

 

 

Ops panel SYSTEM FAULT LED

If the internal temperature

Make sure that the local ambient environment

 

is orange.

 

measured in the airflow

 

temperature is below the upper 104°F (40°C)

An orange LED on one or

 

through the enclosure

 

specification.

 

more power supply module.

 

exceeds a pre-set threshold, a

Check the installation for any airflow restrictions at

An audible alarm is sounding.

 

thermal alarm sounds.

 

either the front or rear of the enclosure. A minimum gap

Air temperature in the exiting

Cooling module failure.

 

of .98 inch (25 mm) at the front and 1.97 inches (50 mm)

 

power supply module is

 

 

 

at the rear is recommended.

 

above 131°F (55°C).

 

 

Check for restrictions caused by dust build-up and clean

 

 

 

 

 

as appropriate.

 

 

 

 

Check for excessive re-circulation of heated air from the

 

 

 

 

 

rear to the front. Installing in a fully enclosed rack

 

 

 

 

 

installation is not recommended.

 

 

 

 

If possible, shutdown the enclosure and investigate the

 

 

 

 

 

problem before continuing.

 

 

 

 

Replace the cooling module.

 

 

 

 

 

 

Thermal warnings

Symptom

Cause

Action

 

 

 

 

 

All orange LEDs on the Ops

The temperature is higher than the

Power off immediately.

 

panel and on all drive bays are

thermal alarm threshold (this should

Check for airflow restrictions.

 

flashing.

already have been activated).

Check for power supply module faults.

The audible alarm sounds

OR - All fans have failed.

Check for excessive local temperatures.

 

almost continuously and

OR - Only 1 fan is operating and the

 

 

 

cannot be muted.

internal temperature is 104°F (40°C) or

 

 

 

 

above.

 

 

 

 

 

 

 

Hardware faults

Make sure that you have obtained a replacement module of the same type before removing any faulty module.

Caution

If your Gateway E-842R enclosure is turned on and you remove any module, replace it immediately. If the enclosure is used with plug-in modules, dummy carriers, or blank modules missing for more than a few minutes, the enclosure can overheat, causing power failure and data loss. Such use invalidates the warranty.

Replace a faulty drive with a drive of the same type and equal or greater capacity.

All drive bays must have a drive carrier or dummy carrier module installed in order to maintain a balanced airflow.

All of the supplied plug-in power supply units, electronics modules, dummy carriers, and blank modules must be installed for the air to flow correctly around the cabinet.