Heat Pump Models

Remote Thermostat Control

Heat Pump Models

The Zoneline® 6100 Series heat pump units may be connected to a single-stage cooling/two-stage heating thermostat designed for use with heat pump systems. GE offers two thermostats compatible with the

6100 series units:

RAK148D1

RAK148P1

solid-state digital

solid-state digital

thermostat

programmable

requiring six

thermostat

connection wires.

requiring six

 

connection wires.

Please see page 55 for installation recommendations for the remote thermostat wiring. Compatibility of other thermostats considered for use with the GE Zoneline unit is the responsibility of the customer.

The control voltage on the remote control conductors is 24 VAC.

The remote thermostat-Class 2 option (Mode 6 in the auxiliary control setting) must be turned ON to enable remote thermostat control. Refer to installation instructions packaged with the chassis.

The fan speed for the 6100 Series in remote thermostat operation is selected by the connection of the fan wire from the thermostat to either the HIGH or LOW terminal on the unit. See the sketch of the unit terminals for the location of the HIGH and LOW fan speed terminals. Operating the unit in low fan speed reduces the operating sound level of the unit.

Field Wiring Terminal

R

— 24V AC

GL

Low-Speed Fan

GH

High-Speed Fan

B

— Reversing Valve

Y

— Compressor

W

— Heater

C

— Common

 

 

Feature
Heat Pump
Electric Heat

Indoor Frost Control

Yes

Yes

Freeze Sentinel

Yes

Yes

Heat Sentinel

Yes

Yes

Auto Fan Speed

No

No

Electronic

 

 

Temperature Limiting

No

No

Switch to Resistance

 

 

Heat Based on Indoor

Determined by

 

Temperature

Remote Thermostat

N/A

Switch to Resistance

 

 

Heat Based on

 

 

Outdoor Temperature

Yes

N/A

Reverse Cycle Defrost

Yes

N/A

Simultaneous

 

 

Resistance Heat

 

 

with Heat Pump

No

N/A

Resistance Heat

 

 

Lockout

Yes

N/A

“Smart Fan”

Fan ON/AUTO Set On

Fan ON/AUTO Set On

Fan Cycle

Remote Thermostat

Remote Thermostat

Central Desk Control

Yes

Yes

When connected to a remote thermostat, the indoor-air- temperature sensing is shifted from the unit to the remote thermostat. For this reason, the units will operate slightly differently when connected to a remote thermostat. The above chart shows the unit operation when connected to a remote thermostat.

Boost heat option should not be used with remote thermostat operation since this will cause the unit to switch to resistance heat when outdoor temperatures are below 46ºF.

CDC

R GL GH B Y W C

Common

White — Heater

Yellow — Compressor

Black — Reversing Valve

Green — High-Speed Fan

Green — Low-Speed Fan

Red — 24V AC

CDC Terminal