GE AE0CD10AM, AE0CD14DM Installation Instructions 2 INSTALLATION cont, 6WIRE THE INDOOR UNIT

Models: AE1RD10AM AE0RD20DM AE0RD10AM AE1CD14DM AE1CD10AM AE0CD20DM AE0RD14DM AE1RD14DM AE1RD20DM AE1CD20DM AE0CD14DM AE0CD10AM

1 56
Download 56 pages 24.81 Kb
Page 12
Image 12
Installation Instructions

Installation Instructions

2 INSTALLATION (cont.)

5CONNECT ELECTRICAL WIRING BETWEEN INDOOR AND OUTDOOR UNITS

All wiring should be rated appropriately for the current value listed on the rating plate.

The power supply should accommodate the rated voltage.

Wiring must be done by a qualified electrician according to local codes, regulations and this manual.

All wiring connections should be tightened securely.

6WIRE THE INDOOR UNIT

NOTE: Use UL-approved electrical branch circuit disconnect for providing supply voltage to split system indoor and outdoor units. Locate disconnect within sight and readily accessible per NEC and local codes.

1.Open the front access panel.

2.Remove the cover plate of the electrical box.

6WIRE THE INDOOR UNIT6WIRE THE INDOOR UNIT (cont.) Access panel

NOTES: Cover plate

3.On the back of the indoor unit, remove the conduit connecting cover. Using the fixing nut, connect the conduit to the connecting cover. Route the wire leads through the unit to the electrical box area. Reinstall the connecting cover.

Back of unit Manual background

Fixing nut Manual backgroundManual backgroundManual background

Connecting cover Manual background

Conduit

6WIRE THE INDOOR UNIT (cont.)

NOTE: Wiring must be done by a qualified electrician according to the local codes and regulations and this manual. The connecting wire should be correctly connected to the circuit interface.

4-way terminal board

Power connection cord

Electrical wires must be secured with attached strain reliefs.

115V Models

Outdoor unit

Indoor unit

Power supply

To branch circuit

Ground

*L1 will be used for neutral in 115V models.

230/208V Models

Outdoor unit

Indoor unit

Power supply

To branch circuit

Ground

NOTES:

Wiring should be consistent with the wiring diagrams above.

Tighten the nut of the terminal board to keep the board secured.

After tightening, the wire cannot be removed if pulled.

Incorrect wiring will cause the air conditioner to work abnormally.

Incorrect grounding will cause a short circuit .

4.Replace the cover plate over the electrical box and lower the access panel into position.

12