9
2
2 Pre-programming settings prior to switchgear arrival
Entellisys provides a method for users to work on the system settin gs before the switchgear
arrives. Once the gear is installed and control power is applied, the saved settings can be written
to the system.
To pre-program Settings, the “Entellisys Remote HMI – User Interactive version” must be
purchased. GE will ship the Remote H MI software, System Administrator Manual (this manual),
and a System Archive when th e switchgear ships from the factory .
The following steps should be performed to begin p re-programming:
Step 1: Install the “Entellisys Remote H MI – User Interactive version” so ftware.
See Installing and configuring remote HMI software onpage 25 for instructions .
Step 2: Install the System Archive provided by GE.
See Restoring an archive on page 38 for instructions.
Step 3: Change to Offline Mode.
See Offline mode on page 29 for instructions and for offline mode capabilities.
Step 4: Set User Settings.
See DEH-231 Entellisys Low Voltage Switch gear System User Manual.
Step 5: Install and Commission the Switchgear.
See Commissioning the switchge ar on page 11 for instructions.
Step 6: Configure the System fo r Remote Communications.
See Configuring the swi tchgear for remote communication s on page21 for instructions.
Step 7: Write saved Settings to Syste m.
See Writing settings to a live sy stem on page 33 for instructions.