Catalog Number: RSEN-W12

Catalog Number: RSEN-W12

INSTALLATION

Coverage

The RSEN-W12 is designed for offices or small rooms up to 300 square feet. Although total coverage of minor motion is 450 square feet, wall switches are normally mounted off-center in a room which reduces the coverage attainable.

Basic Installation Steps

1.Turn off power at the circuit breaker.

2.Wire and mount the switch in standard junction box.
3.Restore power to the circuit.

4.Adjust settings and test.

Location

When installing the RSEN-W12 in a new junction box, choose the switch location carefully to provide optimum coverage of the occupied area. When replacing an existing wall switch, bear in mind that there must be a clear line of sight between the sensor and the area to be covered. Avoid pointing the switch directly into the hallway where it may detect passers-by.

Mounting

CAUTION: Before installing or performing any service on an RSEN-W12, power must be turned off at the circuit breaker panel.

The RSEN-W12 can replace one switch in any standard single or double gang box. It may be installed in the same manner as an ordinary wall switch. Wire the RSEN-W12 as described in the wiring section.

Ratings

120 VAC Ballast or Tungsten Maximum Load: 800 Watts

Minimum Load: One ballast or one incandescent lamp 277 VAC Ballast only

Maximum Load: 1200 Watts

Minimum Load: One ballast

Wiring

CAUTION: The RSEN-W12 is designed for use with either 120 VAC or 277 VAC only. Do not use with any other voltage. Do not wire to control receptacle circuits.

Verify that the connected load does not exceed the RSEN-W12 ratings. Use twist-on wire connectors for all connections. All installations should be in compliance with the NEC and all state and local electrical codes. The RSEN-W12 can be wired to control both an exhaust fan and lighting provided the total load does not exceed the maximum load rating (in Amps) for the automatic wall switch.

Sensor Coverage

12 STEP WALK COVERAGE MOTION-AT-DESK COVERAGE

SENSOR

20 24

(6.1) (7.3)

25 (7.6)

30 (9.1)

feet (meters)

Sensor Location

S

10' x 15' OFFICE

One Circuit – One Lighting Load: Connect one wire to the switchleg for the load. Connect the other wire to the hot lead. Connections are not polarity sensitive.

One Circuit – Two Lighting Loads: The combination of Load 1 and Load 2 must not exceed the maximum load rating. Consult with the building manager and occupant to determine which lights should be off (Load 2) when the toggle switch adjacent to the RSEN-W12 is open (OFF).

Caution: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit to the RSEN-W12. Split one circuit into two switchlegs and cap the unused hot lead inside the box.

The RSEN-W12 must always control Load 1, while its control of Load 2 is selected manually by opening and closing the toggle switch. Connect one wire to the switchleg for Load 1 and one side of the toggle switch for Load 2. Finally, connect the other wire from the RSEN-W12 to the hot lead. Connec- tions are not polarity sensitive.