GE JGP656 installation instructions Duct Fittings, Installation instructions, Flexible ducting

Models: JGP656

1 32
Download 32 pages 13.5 Kb
Page 19
Image 19
Duct Fittings

Installation instructions.

Duct Fittings

Use the chart at the right to compute maximum permissible lengths for duct runs to outdoors.

NOTE: Do not exceed maximum permissible equivalent lengths!

Flexible ducting:

If flexible metal ducting is used, all the equivalent feet values in the table should be doubled. The flexible metal duct should be straight and smooth and extended as much as possible.

Do NOT use flexible plastic ducting.

NOTE: Any home ventilation system, such as a cooktop with a downdraft exhaust mechanism, may interrupt the proper flow of combustion air and exhaust required by fireplaces, gas furnaces, gas water heaters and other naturally vented systems. To minimize the chance of interruption of such naturally vented systems, follow the heating equipment manufacturer’s guidelines and safety standards such as those published by NFPA and

ASHRAE.

 

 

 

Total

 

Equivalent

Number

Equivalent

Duct Pieces

Length*

Used

Length

 

 

 

 

 

 

 

 

 

6round,

1 ft.

 

 

 

 

 

 

 

 

 

 

(per foot

 

 

 

 

 

 

 

 

 

 

straight

length)

feet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

314x 10

1 ft.

 

 

 

 

 

 

 

 

 

 

(per foot

 

 

 

 

 

 

 

 

 

 

straight

length)

feet

 

 

 

 

 

 

 

 

 

6, 90°

15 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

elbow

 

 

 

 

 

 

 

 

 

 

6, 45°

9 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

elbow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

314x 10

16 ft.

 

 

 

 

 

 

 

 

 

 

90° elbow

 

 

 

 

 

 

 

 

 

 

314x 10

5 ft.

 

 

 

 

 

 

 

 

 

 

45° elbow

 

 

 

 

 

 

 

 

 

 

314x 10

18 ft.

 

 

 

 

 

 

 

 

 

 

90° flat elbow

 

 

 

 

 

 

 

 

 

 

6round

 

 

 

 

 

 

 

 

 

 

 

to 314x 10

7 ft.

 

 

 

 

 

 

 

 

 

 

transition

 

 

 

 

 

 

 

 

 

 

314x 10

 

 

 

 

 

 

 

 

 

 

 

to 6round

5 ft.

 

 

 

 

 

 

 

 

 

 

transition

 

 

 

 

 

 

 

 

 

 

6round

 

 

 

 

 

 

 

 

 

 

 

to 314x 10

 

 

 

 

 

 

 

 

 

 

 

transition

20 ft.

 

 

 

 

 

 

 

 

 

 

90° elbow

 

 

 

 

 

 

 

 

 

 

314x 10

 

 

 

 

 

 

 

 

 

 

 

to 6round

 

 

 

 

 

 

 

 

 

 

 

transition

12 ft.

 

 

 

 

 

 

 

 

 

 

90° elbow

 

 

 

 

 

 

 

 

 

 

6round wall

21 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

cap with damper

 

 

 

 

 

 

 

 

 

 

314x 10wall

27 ft.

 

 

 

 

 

 

 

 

cap with damper

 

 

 

 

 

 

 

 

 

 

6round

20 ft.

 

 

 

 

 

 

 

 

 

 

roof cap

 

 

 

 

 

 

 

 

 

 

6round

24 ft.

 

 

 

 

 

 

 

 

 

 

roof vent

 

Total duct run should not exceed 150 ft.

*Actual length of straight duct plus duct fitting equivalent. Equivalent length of duct pieces are based on actual tests conducted by GE Evaluation Engineering and reflect requirements for good venting performance with any downdraft cooktop.

19

Page 19
Image 19
GE JGP656 Duct Fittings, Installation instructions, Flexible ducting, Do NOT use flexible plastic ducting