COMMUNICATIONS GUIDE RS485 INTERFACE (MODBUS RTU)
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE 41
0 Low Speed
1 High Speed
FC136 16 bits Motor Speed During Trip / Motor Speed During Event
0None
1A
2B
FC139 16 bits Starter Type
0None
1 FV Nonreversing
2FV Reversing
3Two Speed
4Wye-Delta
5Inverter
6 Soft Starter
7 Custom Starter
FC140 16 bits Interlock Function
0Disabled
1Trip
2Alarm
3Stop
FC141 16 bits Timer Type
0 Millisecond
1 Second
2 Minute
FC142 16 bits FlexLogic Bit Field EEETTTTTTTSSSSSS S-Bits denotes the
element state or Operator specific data Number of inputs
T-Bits denote Flex logic Operands and Parameters or
when one of the E bits are set they denote specific details
for the Element Type E-Bits
0x0000 OFF
0x0001 ON
0x0040 Contact Inputs
0x0080 Virtual Inputs
0x00C0 Virtual Outputs
0x01C0 Remote Inputs
0x0380 Insert
0x0400 End
0x0440 NOT
0x0480 XOR
0x04C0 LATCH
0x0500 OR
0x0540 AND
0x0580 NOR
0x05C0 NAND
0x0600 TIMER
0x0640 ASSIGN
0x8000 Trip
0xA000 Alarm
Code Type Definition