COMMUNICATIONS GUIDE

 

 

 

 

RS485 INTERFACE (MODBUS RTU)

 

 

 

 

 

 

 

 

 

 

 

 

 

Modbus

Hex

Description

Min

Max

Step

Units

Format

Default

Size in

 

 

 

 

 

 

 

 

 

 

 

Words

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40869

0364

CBCT Ground Trip Level

5

151

1

A

F2*

151

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40870

0365

Ground Trip Delay On Start

0

100

1

s

F2

0

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40871

0366

Ground Alarm Delay On Run

0

60

1

s

F1

10

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40872

0367

Ground Trip Delay On Run

0

50

1

s

F2

0

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40873

0368

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40874

0369

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

LOAD INCREASE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40875

036A

Load Increase Alarm Level

50

151

1

%FLA

F1*

151

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40876

036B

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40877

036C

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40878

036D

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

PHASE UNDERVOLTAGE (REQUIRED=IO_B)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40879

036E

Undervoltage Alarm Level

60

100

1

%MNV

F1*

100

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40880

036F

Undervoltage Alarm Delay

1

60

1

s

F1

30

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40881

0370

Undervoltage Trip Level

60

100

1

%MNV

F1*

100

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40882

0371

Undervoltage Trip Delay

1

60

1

s

F1

30

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40883

0372

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40887

0376

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

AUXILIARY UNDERVOLTAGE PROTECTION (REQUIRED=IO_C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40888

0377

Aux U/V Alarm

60

91

1

%NCV

F1*

91

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40889

0378

Aux U/V Alarm Delay

1

60

1

s

F1

5

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40890

0379

Aux UV Trip

60

91

1

%NCV

F1*

91

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40891

037A

Aux UV Trip Delay

1

60

1

s

F1

5

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40892

037B

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40893

037C

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40894

037D

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

PHASE OVERVOLTAGE (REQUIRED=IO_B)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40895

037E

Overvoltage Alarm Level

101

121

1

%MNV

F1*

121

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40896

037F

Overvoltage Alarm Delay

1

60

1

s

F1

30

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40897

0380

Overvoltage Trip Level

101

121

1

%MNV

F1*

121

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40898

0381

Overvoltage Trip Delay

1

60

1

s

F1

30

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40899

0382

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40900

0383

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40901

0384

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40902

0385

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

PHASE REVERSAL (REQUIRED=IO_B)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40903

0386

Voltage Phase Reversal

0

2

1

---

FC140

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40904

0387

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40905

0388

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40906

0389

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40907

038A

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

VT FUSE FAIL (REQUIRED=IO_B)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40908

038B

VT Fuse Fail

0

2

1

---

FC140

0

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40909

038C

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40910

038D

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE

25

Page 29
Image 29
GE MM300 manual Load Increase, Phase Undervoltage REQUIRED=IOB, Mnv, Auxiliary Undervoltage Protection REQUIRED=IOC, Ncv

MM300 specifications

The GE MM300 is a robust and versatile controller designed primarily for industrial automation applications. Built to tackle the demands of modern manufacturing environments, this controller offers a range of features that contribute to its popularity among engineers and operators.

One of the standout features of the GE MM300 is its scalability. The device can be easily configured to meet the needs of both small and large systems. Its modular architecture allows users to add or remove components based on the specific requirements of their applications, facilitating a more tailored approach to automation.

The MM300 supports various communication protocols, including Ethernet/IP, Modbus TCP, and more, ensuring seamless integration with a variety of devices and systems. This feature significantly enhances interoperability, allowing users to connect the controller to existing infrastructure without extensive reconfiguration.

In terms of processing power, the MM300 is equipped with a high-performance processor that can handle complex tasks with ease. With advanced data handling capabilities, it supports real-time data processing, enabling faster decision-making and improving overall operational efficiency. This capability is particularly beneficial for applications requiring precise control and monitoring.

Moreover, the GE MM300 boasts a user-friendly interface, featuring an intuitive programming environment that simplifies the development of control applications. This includes an integrated development environment (IDE) and support for popular programming languages, making it accessible for both seasoned programmers and those new to automation technologies.

The device is designed to operate in challenging industrial conditions, featuring a rugged construction that ensures durability and longevity. Its ability to withstand extreme temperatures, vibrations, and other environmental stressors enhances its reliability in demanding applications, which is crucial for minimizing downtime in production processes.

Security is another critical aspect of the GE MM300. The controller incorporates advanced security features to protect against unauthorized access and cyber threats, helping organizations ensure the integrity of their operations.

In summary, the GE MM300 stands out due to its scalability, versatile communication options, high processing capabilities, user-friendly programming environment, rugged design, and security features. These characteristics make it a reliable choice for industries seeking to enhance their automation processes and improve overall efficiency. Whether for small-scale or large-scale applications, the MM300 provides a comprehensive solution to meet the evolving needs of modern manufacturing.