COMMUNICATIONS GUIDE RS485 INTERFACE (MODBUS RTU)
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE 37
2RTD #2
3RTD #3
4RTD #4
5RTD #5
6RTD #6
FC126 16 bits Disabled / Enabled Selection
0Disabled
1 Enabled
FC128 16 bits Command Status
0Manual
1Auto
2 Manual Inhibit
3 Auto/ Manual
4Hardwired Auto
5None
FC129 16 bits Quick Status Status
Bit 0 Alarm
Bit 1 Trip
Bit 2 Self Test Fault
Bit 3 Auto
Bit 4 Contactor A
Bit 5 Contactor B
Bit 6 Contact Output 3
Bit 7 Drive Available
FC130 16 bits LED Flash
Bit 0 Running
Bit 1 Stopped
Bit 2 Tripped
Bit 3 Alarm
Bit 4 Comms OK
Bit 5 Auto
Bit 6 Manual
Bit 7 USER1
Bit 8 USER2
Bit 9 USER3
Bit 10 50%
Bit 11 80%
Bit 12 100%
FC131 16 bits Comm Fail Mode
1 Serial
2 Serial & Ethernet
4 Serial & FieldBus
8Ethernet
16 FieldBus
32 Ethernet & Fieldbus
64 All
FC134 16 bits Cause of Event
Code Type Definition