Safety Instructions
Installation of the range.
Connect the Range to the Electrical Supply
Skip to Step 5 if the power cord shipped on the range does not match your wall receptacle.
Using an Existing NEMA 14-50R Receptacle
Operating Instructions
■Plug the range power cord into a properly grounded wall receptacle. Skip to Step 6 if the range power cord matches the wall receptacle.
NOTE: Your range is shipped with a
Effective January 1, 1996, the National Electrical Code requires that new construction (not existing) utilize a
A range cord rated at 40 amps with 125/250 minimum volt range is required. A
NOTE: A
Replace the Power Cord (Optional)
Perform this step only if the power cord shipped on the range does not match your wall receptacle.
Installation | Instructions |
Consumer Support Troubleshooting Tips
Remove the wire cover (on the back of the range) by removing two (2) screws using a 1/4” nut driver.
Do not discard these screws.2 screws to remove wire cover
Retaining tab
Back of range
Wire cover
Remove the 3 lower power cord terminal screws from the terminal block and the ground screw and plate.
Terminal | Neutral terminal | |
block | ||
|
Ground plate |
(grounding to |
range) |
46 | Ground |
screw |
Place the terminal screws and ground screw in safe location for later use.
Loosen the strain relief screws and remove the power cord.
NOTE: The replacement power cord must be a
Follow the