Installation
Electrical Requirements
GROUNDING SPECIFICATIONS
Ground Path Resistance 0.10 Ω Max.
Insulation Resistance 250K Ω Min.
POWER SUPPLY REQUIREMENTS
The cooktop must be connected to a supply circuit of the proper voltage and frequency as specified on the nomenclature tag. Wire size must conform to the National Electrical Code or the prevailing local code. The nomenclature tag is located on the bottom of the burner box.
OVERCURRENT PROTECTION
WIRING
WARNING: Improper connection of aluminum house wiring to these copper leads can result in a serious problem. Use only connectors designed for joining copper to aluminum and follow the manufacturer’s recommended procedure closely.
WIRING REQUIREMENTS
WARNING: This appliance must be properly grounded.
NEC RATING | MAXIMUM KILOWATT RATING | All cooktops must be hard wired (direct wired) | |||
| 208V | 236V | 240V | ||
| into an approved junction box. The junction box | ||||
20 Amp | 4.2 | 4.7 | 4.8 | ||
30 Amp | 6.2 | 7.1 | 7.2 | must be easily reached through the front of the | |
35 Amp | 7.3 | 8.3 | 8.4 | cabinet where the cooktop will be located. Allow | |
40 Amp | 8.3 | 9.4 | 9.6 | considerable slack in the conduit for serviceability. | |
50 Amp | 10.4 | 11.8 | 12.0 | ||
A “plug and receptacle” is not permitted on these | |||||
|
|
|
| ||
|
|
|
| products. |
The branch circuit load for 1
The branch circuit load for a
You must use a
Refer to the nomenclature tag on your cooktop for the KW rating for your cooktop.
– 6 –