Goodman Mfg A/GPG13 M operating instructions GPG1336***M43A* - COOLING SPEEDS

Models: A/GPG13 M

1 36
Download 36 pages 49.77 Kb
Page 24
Image 24
GPG1336***M43A* - COOLING SPEEDS

BLOWER PERFORMANCE DATA - COOLING SPEEDS THREE PHASE

GPG1336***M43A* - COOLING SPEEDS

Unit

 

HIGH (Cooling Speed)

 

 

MEDIUM (Cooling Speed)

 

 

LOW (Cooling Speed)

 

Static

CFM

Watts

RPM

 

Amps

CFM

 

Watts

RPM

 

Amps

CFM

Watts

RPM

 

Amps

0.1

1,655

604

878

 

2.67

1,469

 

494

804

 

2.24

1,100

342

665

 

1.57

0.2

1,579

587

903

 

2.68

1,409

 

480

833

 

2.15

1,037

335

697

 

1.52

0.3

1,483

567

925

 

2.62

1,327

 

459

866

 

2.08

991

320

760

 

1.45

0.4

1,407

547

953

 

2.53

1,257

 

442

903

 

2

926

308

818

 

1.39

0.5

1,329

522

980

 

2.44

1,163

 

419

942

 

1.89

831

290

872

 

1.32

0.6

1,210

498

1,004

 

2.35

1,094

 

398

968

 

1.8

773

279

902

 

1.25

0.7

1,036

464

1,033

 

2.24

942

 

363

1,002

 

1.65

669

260

945

 

1.17

0.8

-

-

-

 

-

-

 

-

-

 

-

-

-

-

 

-

 

GPG1348***M43A* - Rise Range: 45° - 75°

 

Unit

T4 COOLING SPEED

T5 COOLING SPEED

Static

CFM

WATTS

AMPS

CFM

WATTS

AMPS

0.1

--------

--------

--------

--------

--------

--------

0.2

1,593

449

3.55

1,669

532

4.22

0.3

1,545

463

3.69

1,654

239

4.25

0.4

1,506

476

3.82

1,610

551

4.30

0.5

1,448

481

3.87

1,545

557

4.36

0.6

1,400

493

3.95

1,512

566

4.41

0.7

1,341

502

4.00

1,433

578

4.59

0.8

1289

511

4.11

1,392

591

4.65

 

 

GPG1360***M43A* - COOLING SPEEDS

 

 

Unit

 

T4 (Cooling Speed)

 

 

T5 (Cooling Speed)

 

Static

CFM

WATTS

RPM

AMPS

CFM

WATTS

RPM

AMPS

0.1

1942

649

993

4.83

2067

792

1054

5.81

0.2

1883

657

1010

4.87

2030

811

1077

5.85

0.3

1859

670

1029

4.96

1982

814

1088

5.88

0.4

1827

675

1047

4.97

1909

808

1101

5.86

0.5

1749

683

1069

4.99

1842

798

1110

5.85

0.6

1706

693

1083

5.10

1789

772

1117

5.65

0.7

1655

703

1104

5.12

1703

763

1129

5.58

0.8

1588

705

1120

5.11

1618

732

1135

5.29

NR = Heating Temperature Rise Not Recommended.