Goodman Mfg A/GPG13 M operating instructions GPG1348,603** WIRING DIAGRAM, Installer/Serviceman

Models: A/GPG13 M

1 36
Download 36 pages 49.77 Kb
Page 34
Image 34
Manual background

GPG13(48,60)3** WIRING DIAGRAM

HIGH VOLTAGE!

DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS

UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO

DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

L1

 

 

SUPPLY VOLTAGE

 

L2

 

 

L3

COMPONENT LEGEND

FACTORY WIRING

 

 

 

 

208-230/3/60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALS

AUXILIARY LIMIT SWITCH

LINE VOLTAGE

 

 

 

 

CH

 

NOTE 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMP

COMPRESSOR

LOW VOLTAGE

 

 

 

 

 

 

T2

C

 

 

 

 

CM

CONDENSER MOTOR

OPTIONAL HIGH VOLTAGE

 

C

T1

 

T2

 

 

 

 

 

 

 

C

CONTACTOR

 

 

 

 

T1

 

T3

 

 

 

 

 

 

L3

CH

CRANKCASE HEATER

FIELD WIRING

 

 

 

 

 

 

T3

C

 

 

EM

EVAPORATOR MOTOR

 

 

 

 

 

 

 

 

 

 

F

FUSE

HIGH VOLTAGE

 

 

 

 

FC

 

 

 

 

 

 

 

 

 

 

 

 

CM

 

 

 

 

 

FC

FAN CAPACITOR

LOW VOLTAGE

 

 

 

 

 

 

 

 

 

 

 

FS

FLAME SENSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

GND

EQUIPMENT GROUND

WIRE CODE

 

 

N

 

 

 

 

VMR

 

 

GV

GAS VALVE

BK

BLACK

 

 

EM

 

 

 

 

 

 

IIC

INTEGRATED IGNITION CONTROL

 

 

 

 

 

 

VM

 

 

 

BL

BLUE

 

 

 

 

 

 

 

 

4

 

 

IGN

IGNITOR

BR

BROWN

 

 

 

 

 

3

2

1

 

 

 

 

LS

LIMIT SWITCH

GR

GREEN

 

 

 

 

 

 

 

 

 

PLF

FEMALE PLUG/CONNECTOR

OR

ORANGE

 

 

 

 

 

 

 

 

 

 

 

NOTE 7

 

 

 

 

TR

NOTE 7

 

 

 

PS

PRESSURE SWITCH

PK

PINK

1

 

 

 

 

 

 

 

2

RS

ROLLOUT SWITCH

PU

PURPLE

 

 

 

 

 

 

IGN

 

 

IIC

TR

TRANSFORMER

RD

RED

 

 

 

 

FS

 

 

FS

 

 

VM

VENT MOTOR

WH

WHITE

 

 

 

 

 

 

 

 

 

 

 

F

 

C

 

 

 

 

 

 

VMR

VENT MOTOR RELAY

YL

YELLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EM C

 

 

 

HPS

HIGH PRESSURE SWITCH

BL/PK BLUE/PINK

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

D1

 

 

1

3

 

 

 

NOTES

 

 

 

 

 

 

 

 

LS

VMR

 

 

 

1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSULATION AS ORIGINAL .(USE COPPER CONDUCTOR ONLY).

 

 

IIC

3

 

 

ALS

RS

 

 

 

 

2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE

 

 

 

 

 

 

GV

 

 

 

FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.

 

 

 

 

6

 

 

 

 

 

 

 

 

3. CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS.

 

 

 

 

 

 

PS

 

 

 

 

 

4. FOR DIFFERENT THAN FACTORY SPEED TAP. CHANGE COOLING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

SPEED AT MOTOR T4 AND T5 TERMINALS. CHANGE HEATING

9

 

7

10

12

 

 

 

 

 

 

 

SPEED AT MOTOR T1, T2 AND T3 TERMINALS.

 

 

 

 

 

 

 

 

 

COOLING SPEED (YELLOW WIRE)

HEATING SPEED (WHITE WIRE)

 

 

 

 

11

 

 

HPS

C

 

 

 

 

 

 

 

 

 

 

 

 

T4 - LOW SPEED

T1 - LOW SPEED

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T5 - HIGH SPEED

T2 - MED. SPEED

 

 

 

 

 

 

 

 

NOTE

 

 

 

 

 

 

 

 

 

 

 

6

5

4

 

 

T3 - HIGH SPEED

 

 

 

 

 

 

 

 

PLF

5. ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS) ADJACENT

 

 

 

 

 

 

 

 

 

 

 

R

 

G

W

Y1

 

Y/Y2

 

3

2

1

TO BLOWER HOUSING IN RETURN AIR COMPARTMENT.

 

 

 

 

C

 

 

 

6. USE COOPER CONDUCTORS ONLY.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO THERMOSTAT

 

 

 

 

 

 

 

 

 

USE NEC CLASS 2 WIRE.

 

 

 

 

 

 

 

 

 

 

7. L1 AND L2 ON ICC CONTROL IS 24V INPUT.

208-230/3/60

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTALLER/SERVICEMAN

 

 

THERMOSTAT FIELD WIRING

 

 

 

 

 

 

STATUS LIGHT

EQUIP. STATUS

CHECK

 

 

2 STAGE COOLING WITH ECONOMIZER

 

 

OPTION

 

ON

NORMAL OPERATION

-

 

 

 

NO ECONOMIZER

 

 

 

OFF

NO POWER OR

 

 

WH

W

 

 

 

 

INTERNAL CONTROL

 

 

 

 

FAULT

 

WH

W

GR

G

1 BLINK

IGNITION FAILURE

GAS FLOW

GR

G

RD

R

 

OR

GAS PRESSURE

 

OPEN ROLLOUT

GAS VALVE

 

R

 

 

 

SWITCH

FLAME SENSOR

RD

PU

Y1

 

OR

FLAME ROLLOUT

YL

Y

 

 

 

OPEN AUX. LIMIT

BAD SWITCH

YL

Y2

 

SWITCH

AUX. LIMIT OPEN

BL

C

BL

C

2 BLINKS

PRESSURE SWITCH

CHECK

 

OPEN

PRESSURE SWITCH

 

 

 

 

3 BLINKS

WITHOUT INDUCER ON

CHECK

 

 

 

 

 

PRESSURE SWITCH

 

 

 

 

4 BLINKS

OPEN LIMIT SWITCH

MAIN LIMIT OPEN

 

 

 

 

 

 

BAD SWITCH

 

 

 

 

5 BLINKS

FALSE FLAME SENSED

 

 

 

0140G01002 REV. A

6 BLINKS

COMPRESSOR

3 MIN. COMP.

 

 

 

 

 

 

 

OUTPUT DELAY

 

 

 

 

 

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

34

Page 34
Image 34
Goodman Mfg A/GPG13 M operating instructions GPG1348,603** WIRING DIAGRAM, Installer/Serviceman