Goodman Mfg A/GPG13 M operating instructions Natural Gas Connection, Proper Piping Practice

Models: A/GPG13 M

1 36
Download 36 pages 49.77 Kb
Page 7
Image 7
Natural Gas Connection

PIPING

IMPORTANT NOTE: To avoid possible unsatisfactory operation or equipment damage due to under firing of equipment, do not un- dersize the natural/propane gas piping from the meter/tank to the unit. When sizing a trunk line, include all appliances on that line that could be operated simultaneously.

The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. The gas line installation must comply with local codes, or in the absence of local codes, with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1.

Natural Gas Connection

Natural Gas Capacity of Pipe

in Cubic Feet of Gas Per Hour (CFH)

Length of

 

Nominal Black Pipe Size (inches)

 

 

 

 

 

 

 

 

Pipe in Feet

1/2

 

3/4

1

1 1/4

 

1 1/2

10

132

 

278

520

1050

 

1600

20

92

 

190

350

730

 

1100

30

73

 

152

285

590

 

980

40

63

 

130

245

500

 

760

50

56

 

115

215

440

 

670

60

50

 

105

195

400

 

610

70

46

 

96

180

370

 

560

80

43

 

90

170

350

 

530

90

40

 

84

160

320

 

490

100

38

 

79

150

305

 

460

Pressure = .50 PSIG or less and Pressure Drop of 0.3" W.C. (Based

on 0.60 Specific Gravity Gas)

CFH =

BTUH Furnace Input

Heating Value of Gas (BTU/Cubic Foot)

 

Refer to the Proper Piping Practice drawing for the general layout at the unit. The following rules apply:

1.Use black iron pipe and fittings for the supply piping. The use of a flex connector and/or copper piping is permitted as long as it is in agreement with local codes.

2.Use pipe joint compound on male threads only. Pipe joint compound must be resistant to the action of the fuel used.

3.Use ground joint unions.

4.Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long.

5.Use two pipe wrenches when making connection to the gas valve to keep it from turning.

6.Install a manual shut-off valve in a convenient location (within six feet of unit) between the meter and the unit.

7.Tighten all joints securely.

8.The unit must be connected to the building piping by one of the following methods:

Rigid metallic pipe and fittings

Semirigid metallic tubing and metallic fittings (Aluminum alloy tubing must not be used in exterior locations)

Listed gas appliance connectors used in accordance with the terms of their listing that are completely in the same room as the equipment

In the prior two methods above the connector or tubing must be protected from physical and thermal damage. Aluminum alloy tubing and connectors must be coated to protect against external corrosion when in contact with masonry, plaster or insulation or are subject to repeated wettings by liquids (water - not rain water, detergents or sewage)

MANUAL

SHUT-OFF

VALVE

DRIP LEG

GROUND JOINT UNION

(INSTALLED AHEAD OF GAS VALVE)

GROMMET

Proper Piping Practice

NOTE: The unit gas supply entrance is factory sealed with plugs. Keep plugs in place until gas supply is ready to be installed. Once ready, replace the plugs with the supplied grommets and install gas supply line.

GAS PIPING CHECKS

Proper Piping PracticeCAUTION

TO PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, THE FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GAS CONNECTIONS AND PRESSURE TESTING:

THE UNIT AND ITS GAS CONNECTIONS MUST BE LEAK TESTED BEFORE PLACING IN OPERATION. BECAUSE OF THE DANGER OF EXPLOSION OR FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS. NEVER EXCEED SPECIFIED PRESSURES FOR TESTING. HIGHER PRESSURE MAY

DAMAGE GAS VALVE AND CAUSE OVERFIRING WHICH MAY RESULT IN PREMATURE HEAT EXCHANGE FAILURE.

THIS UNIT AND ITS SHUT-OFF VALVE MUST BE DISCONNECTED FROM

THE GAS SUPPLY DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF 1/2 PSIG (3.48 KPA).

THIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY SYSTEM BY CLOSING ITS MANUAL SHUT-OFF VALVE DURING ANY PRESSURE

TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (3.48 KPA).

Manual backgroundWARNING

TO AVOID PROPERTY DAMAGE OR PERSONAL INJURY, BE SURE THERE IS

NO OPEN FLAME IN THE VICINITY DURING AIR BLEEDING.

There will be air in the gas supply line after testing for leaks on a new installation. Therefore, the air must be bled from the line by loosening the ground joint union until pure gas is expelled. Tighten union and wait for five minutes until all gas has been dissipated in the air. Be certain there is no open flame in the vicinity during air bleeding procedure. The unit is placed in operation by closing the main electrical disconnect switch for the unit.

7

Page 7
Image 7
Goodman Mfg A/GPG13 M operating instructions Natural Gas Connection, Proper Piping Practice