Goodman Mfg A/GPG13 M operating instructions Blower Performance Data - Single Phase

Models: A/GPG13 M

1 36
Download 36 pages 49.77 Kb
Page 19
Image 19
BLOWER PERFORMANCE DATA - SINGLE PHASE

BLOWER PERFORMANCE DATA - SINGLE PHASE

 

 

 

 

*PG1324045M41A* - Rise Range: 30° - 60°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

 

LOW

 

 

MEDIUM

 

 

HIGH

 

Static

CFM

WATTS

AMPS

RISE

CFM

WATTS

AMPS

RISE

CFM

WATTS

AMPS

RISE

0.1

600

150

0.67

57

850

230

1.02

40

1,190

380

1.67

NR

0.2

570

140

0.65

60

830

220

1.00

41

1,140

360

1.62

NR

0.3

510

130

0.63

NR

765

215

0.97

45

1,080

350

1.58

32

0.4

450

125

0.61

NR

715

210

0.94

48

1,025

340

1.54

33

0.5

380

120

0.58

NR

660

205

0.90

52

975

330

1.38

35

0.6

--------

--------

--------

NR

610

195

0.88

56

920

310

1.37

37

0.7

--------

--------

--------

NR

--------

--------

--------

NR

830

300

1.35

41

0.8

--------

--------

--------

NR

--------

--------

--------

NR

730

290

1.32

47

*PG1324070M41A* - Rise Range: 35° - 65°

Unit

 

LOW

 

 

MEDIUM

 

 

HIGH

 

Static

CFM

WATTS

AMPS

RISE

CFM

WATTS

AMPS

RISE

CFM

WATTS

AMPS

RISE

0.1

600

150

0.67

NR

850

230

1.02

NR

1,190

380

1.67

43

0.2

570

140

0.65

NR

830

220

1.00

NR

1,140

360

1.62

45

0.3

510

130

0.63

NR

765

215

0.97

NR

1,080

350

1.58

47

0.4

450

125

0.61

NR

715

210

0.94

NR

1,025

340

1.54

50

0.5

380

120

0.58

NR

660

205

0.90

NR

975

330

1.38

52

0.6

--------

--------

--------

NR

610

195

0.88

NR

920

310

1.37

56

0.7

--------

--------

--------

NR

--------

--------

--------

NR

830

300

1.35

62

0.8

--------

--------

--------

NR

--------

--------

--------

NR

730

290

1.32

NR

*PG1330045M41A* - Rise Range: 30° - 60°

Unit

 

LOW

 

 

MEDIUM

 

 

HIGH

 

Static

CFM

WATTS

AMPS

RISE

CFM

WATTS

AMPS

RISE

CFM

WATTS

AMPS

RISE

0.1

1,056

350

1.51

33

1,261

452

1.95

NR

1,370

509

2.23

NR

0.2

1,010

339

1.43

34

1,221

442

1.90

NR

1,310

492

2.13

NR

0.3

971

343

1.45

36

1,174

428

1.84

NR

1,262

489

2.09

NR

0.4

937

329

1.41

37

1,125

414

1.80

31

1,208

475

2.06

NR

0.5

878

318

1.27

39

1,063

398

1.70

32

1,140

453

1.93

30

0.6

811

306

1.29

43

1,004

380

1.66

34

1,081

440

1.90

32

0.7

723

291

1.21

48

919

368

1.59

38

1,006

425

1.88

34

0.8

545

259

1.10

NR

796

371

1.46

43

879

403

1.74

39

*PG133070M41A* - Rise Range: 35° -65°

Unit

 

LOW

 

 

MEDIUM

 

 

HIGH

 

Static

CFM

WATTS

AMPS

RISE

CFM

WATTS

AMPS

RISE

CFM

WATTS

AMPS

RISE

0.1

1,056

350

1.51

49

1,261

452

1.95

41

1,370

509

2.23

38

0.2

1,010

339

1.43

51

1,221

442

1.90

42

1,310

492

2.13

40

0.3

971

343

1.45

53

1,174

428

1.84

44

1,262

489

2.09

41

0.4

937

329

1.41

55

1,125

414

1.80

46

1,208

475

2.06

43

0.5

878

318

1.27

59

1,063

398

1.70

49

1,140

453

1.93

45

0.6

811

306

1.29

64

1,004

380

1.66

52

1,081

440

1.90

48

0.7

723

291

1.21

NR

919

368

1.59

56

1,006

425

1.88

NR

0.8

545

259

1.10

NR

796

371

1.46

65

879

403

1.74

NR

NR = Heating Temperature Rise Not Recommended.