(b)All Air from Outdoors: The confined space shall be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
1.When directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure.
Chimney or Gas Vent
Outlet air duct
Water
Furnace Heater
Inlet air duct
NOTE: The air duct openings must have a free area of not less than one square inch per 2000 BTU of the total input rating of all equipment in the enclosure*.
Alternate air inlet
Chimney or Gas Vent
Ventilation louvers (each end of attic)
NOTE: The inlet and outlet air openings must each have a free area of not less than one square inch per 4000 BTU of the
total input rating of all equipment in the enclosure.
|
|
|
| Outlet Air | |
|
|
|
|
| |
|
|
|
|
| |
|
|
| Water | ||
|
|
| Heater |
| |
Furnace | Inlet Air | ||||
|
| ||||
|
|
|
|
Ventilation louvers for unheated crawl space
*If the appliance room is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area of not less than one square inch per 4,000 BTU per hour of the total input rating of all appliances in the enclosure.
Equipment Located in Confined Spaces;
All Air from Outdoors. See
4.When ducts are used, they shall be of the same cross- sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall not be less than 3 inches.
Equipment Located in Confined Spaces; All Air from
See
2.When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure.
Chimney or Gas Vent
Ventilation louvers (each end of attic)
NOTE: The inlet and outlet air openings must each have a free area of not less than one square inch per 4000 BTU of the
total input rating of all equipment in the enclosure.
|
|
|
|
|
|
|
|
|
|
|
|
|
| Outlet Air | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| W ater | ||||
|
|
|
|
|
|
|
|
|
|
| Heater |
|
|
| |
|
|
|
| Furnace | Inlet air duct | ||||||||||
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| [ends 1 ft (300 mm) | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| above floor] | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Equipment Located in Confined Spaces; All Air from Outdoors
Through Ventilated Attic. See
3.When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 BTU per hour of total input rating of all equipment in the enclosure.
NOTE: The single opening must have | Chimney or Gas Vent |
a free area of not less than one | |
square inch per 3000 BTU of |
|
the total input rating of all equip- |
|
ment in the enclosure, but not less than |
|
the sum of the areas of all vent |
|
connectors in the confined space. |
|
|
|
|
|
|
|
| Opening |
|
|
|
|
|
|
| Alternate |
|
|
|
|
|
| ||
|
|
|
| Water |
| ||
|
|
|
|
|
| Opening | |
|
|
|
| Heater |
| ||
|
|
|
| ||||
|
|
|
|
| Location | ||
Furnace |
|
|
|
|
| ||
|
|
|
|
|
Equipment Located in Confined Spaces; All Air from Outdoors -
Single Air Opening. See
5.One permanent opening may be permitted, provided the equipment has clearances of at least 1” from the sides and back and 6” from the front. The opening shall communicate directly with the outdoors and must be located within 12” of the top of the enclosure. The minimum free area of the opening shall be 1 square inch per 3,000 BTU per hour of total input rating of all equipment in the enclosure. The minimum free area shall not be less than the sum of the areas of all vent connectors in the confined space.
5.3.4Specially Engineered Installations:
The requirements of 5.3.3 shall not necessarily govern when special engineering, approved by the authority having jurisdiction, provides an adequate supply of air for combustion, ventilation, and dilution of flue gases.