(b)All Air from Outdoors: The confined space shall be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.

1.When directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure.

a free area of not less than one Chimney or Gas Vent

Outlet air duct

Water

Furnace Heater

Inlet air duct

NOTE: The air duct openings must have a free area of not less than one square inch per 2000 BTU of the total input rating of all equipment in the enclosure*.

Alternate air inlet

square inch per 3000 BTU of Chimney or Gas Vent

Ventilation louvers (each end of attic)

NOTE: The inlet and outlet air openings must each have a free area of not less than one square inch per 4000 BTU of the

total input rating of all equipment in the enclosure.

 

 

 

 

Outlet Air

 

 

 

 

 

 

 

 

 

 

 

 

 

Water

 

 

 

Heater

 

Furnace

Inlet Air

 

 

 

 

 

 

Ventilation louvers for unheated crawl space

*If the appliance room is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area of not less than one square inch per 4,000 BTU per hour of the total input rating of all appliances in the enclosure.

Equipment Located in Confined Spaces;

All Air from Outdoors. See 5.3.3-b.

4.When ducts are used, they shall be of the same cross- sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall not be less than 3 inches.

Equipment Located in Confined Spaces; All Air from Outdoors—Inlet Air from Ventilated Crawl Space and Outlet Air to Ventilated Attic.

See 5.3.3-b

2.When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure.

the total input rating of all equip- Chimney or Gas Vent

Ventilation louvers (each end of attic)

NOTE: The inlet and outlet air openings must each have a free area of not less than one square inch per 4000 BTU of the

total input rating of all equipment in the enclosure.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outlet Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W ater

 

 

 

 

 

 

 

 

 

 

 

Heater

 

 

 

 

 

 

 

Furnace

Inlet air duct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[ends 1 ft (300 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

above floor]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Equipment Located in Confined Spaces; All Air from Outdoors

Through Ventilated Attic. See 5.3.3-b.

3.When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 BTU per hour of total input rating of all equipment in the enclosure.

NOTE: The single opening must have

Chimney or Gas Vent

a free area of not less than one

square inch per 3000 BTU of

 

the total input rating of all equip-

 

ment in the enclosure, but not less than

 

the sum of the areas of all vent

 

connectors in the confined space.

 

 

 

 

 

 

 

 

Opening

 

 

 

 

 

 

 

Alternate

 

 

 

 

 

 

 

 

 

 

Water

 

 

 

 

 

 

 

Opening

 

 

 

 

Heater

 

 

 

 

 

 

 

 

 

 

Location

Furnace

 

 

 

 

 

 

 

 

 

 

Equipment Located in Confined Spaces; All Air from Outdoors -

Single Air Opening. See 5.3.3-b.

5.One permanent opening may be permitted, provided the equipment has clearances of at least 1” from the sides and back and 6” from the front. The opening shall communicate directly with the outdoors and must be located within 12” of the top of the enclosure. The minimum free area of the opening shall be 1 square inch per 3,000 BTU per hour of total input rating of all equipment in the enclosure. The minimum free area shall not be less than the sum of the areas of all vent connectors in the confined space.

5.3.4Specially Engineered Installations: