CONDENSING UNIT SPECIFICATIONS

VSX130[18 & 60]1B*

 

 

 

 

 

 

VSX130181B*

VSX130601B*

 

 

 

 

 

 

 

Cooling Capacity, BTUH

18,000

60,000

 

 

SEER/EER

13 / 11

13 / 11

 

 

 

 

 

 

 

Compressor

 

 

 

 

R.L. Amps

6.70

25.0

 

 

L.R. Amps

40.0

134.0

 

 

High Pressure Switch

 

 

 

 

Open

N/A

N/A

 

 

Close

N/A

N/A

 

 

Condenser Fan Motor

 

 

 

 

Horsepower

1/6

1/4

 

 

F.L. Amps

1.10

1.50

 

 

Liquid Line, Inches O.D.*

3/8"

3/8"

 

 

Suction Line, Inches O.D.*

3/4"

1 1/8"

 

 

Refrigerant Charge

71.0

125.0

 

 

Power Supply

208/230-60-1

208/230-60-1

 

 

Minimum Circuit Ampacity(1)

9.5

26.3

 

 

Maximum Overcurrent Device(2)

15

45

 

 

Electrical Conduit Size

 

 

 

 

Power Supply (Inches)

1/2 or 3/4

1/2 or 3/4

 

 

Approximate Shipping Weight

135

200

 

 

(1)Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

(2)Maximum Overcurrent Protection Device: MUST use time delay fuses or HACR-type Circuit Breakers of the same size as noted.

NOTES:

*Always check the S&R plate for electrical data on the unit being installed.

*Installer will need to supply 7/8" to 1 1/8" adapters for suction line connections.

*Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.

*Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT NOT THE INDOOR COIL.

NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.

11

Page 11
Image 11
Goodman Mfg GSX service manual VSX13018 & 601B