EXPANDED PERFORMANCE DATA

 

 

 

COOLING OPERATION

 

MODEL: GSX13048-1AA / CA*F4860*6** / ZP39K5E-PFV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

 

 

 

75

 

 

 

85

 

 

 

 

95

 

 

105

 

 

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering Indoor Wet Bulb Temperature

 

 

 

 

 

 

 

 

 

 

 

IDB*

 

Airflow

 

59

63

 

67

71

59

63

 

67

71

59

63

 

67

 

71

59

63

 

67

71

59

63

67

71

59

63

67

71

 

 

 

 

 

MBh

46.7

47.7

 

50.9

54.4

45.6

46.6

 

49.7

53.2

44.5

45.5

 

48.6

 

51.9

43.4

44.3

 

47.4

50.6

41.2

42.1

45.0

48.1

38.2

39.0

41.7

44.6

 

 

 

 

 

S/T

0.94

0.88

0.72

0.54

1.00

0.91

0.74

0.56

1.00

0.94

0.76

 

0.57

1.00

0.97

0.79

0.59

1.00

1.00

0.82

0.61

1.00

1.00

0.82

0.62

 

 

 

 

1800

Delta T

22

21

19

15

23

22

19

15

23

22

19

 

15

22

22

19

15

21

22

19

15

20

20

18

14

 

 

 

 

KW

3.21

3.28

3.38

3.50

3.46

3.54

3.65

3.78

3.69

3.77

3.89

 

4.03

3.88

3.97

4.10

4.25

4.05

4.14

4.28

4.43

4.20

4.29

4.44

4.59

 

 

 

 

 

AMPS

11.8

12.1

12.5

13.0

12.8

13.1

13.5

14.1

13.9

14.3

14.8

 

15.3

14.9

15.3

15.8

16.4

15.9

16.3

16.8

17.5

16.9

17.3

17.9

18.6

 

 

 

 

 

HI PR

240

259

273

285

270

290

306

320

307

330

349

 

363

349

376

397

414

393

423

447

466

434

467

493

515

 

 

 

 

 

LO PR

112

120

130

139

119

126

138

147

123

131

143

 

153

130

138

150

160

136

144

158

168

140

149

163

174

 

 

 

 

 

MBh

45.3

46.3

49.5

52.9

44.2

45.2

48.3

51.6

43.2

44.1

47.2

 

50.4

42.1

43.1

 

46.0

49.2

40.0

40.9

43.7

46.7

37.1

37.9

40.5

43.3

 

 

 

 

 

S/T

0.90

0.84

0.68

0.51

0.93

0.87

0.71

0.53

0.95

0.89

0.73

 

0.54

0.98

0.92

 

0.75

0.56

1.00

0.96

0.78

0.58

1.00

0.96

0.78

0.59

 

 

80

 

1600

Delta T

23

22

19

16

24

23

20

16

24

23

20

 

16

24

23

 

20

16

23

22

20

16

21

21

18

15

 

 

 

KW

3.18

3.25

3.36

3.47

3.43

3.51

3.62

3.75

3.66

3.74

3.86

 

3.99

3.85

3.94

 

4.07

4.21

4.02

4.11

4.25

4.39

4.16

4.26

4.40

4.55

 

 

 

 

 

AMPS

11.7

12.0

12.4

12.9

12.7

13.0

13.4

13.9

13.8

14.1

14.6

 

15.2

14.8

15.1

 

15.7

16.3

15.7

16.1

16.7

17.3

16.7

17.1

17.7

18.4

 

 

 

 

 

HI PR

238

256

270

282

267

287

303

316

304

327

345

 

360

346

372

 

393

410

389

419

442

461

430

463

488

510

 

 

 

 

 

LO PR

111

118

129

138

118

125

136

145

122

130

142

 

151

128

136

 

149

159

134

143

156

166

139

148

162

172

 

 

 

 

 

MBh

41.8

42.7

45.6

48.8

40.8

41.7

44.6

47.7

39.9

40.7

43.5

 

46.5

38.9

39.7

 

42.5

45.4

36.9

37.8

40.3

43.1

34.2

35.0

37.4

39.9

 

 

 

 

 

S/T

0.86

0.81

0.66

0.49

0.90

0.84

0.68

0.51

0.92

0.86

0.70

 

0.52

0.95

0.89

0.72

0.54

0.98

0.92

0.75

0.56

0.99

0.93

0.76

0.57

 

 

 

 

 

Delta T

24

23

20

16

24

23

20

16

24

23

20

 

16

24

23

20

16

24

23

20

16

22

21

19

15

 

 

 

 

1400

KW

3.10

3.17

3.27

3.38

3.35

3.42

3.53

3.65

3.56

3.64

3.76

 

3.89

3.75

3.84

3.97

4.10

3.91

4.00

4.14

4.28

4.05

4.15

4.29

4.43

 

 

 

 

 

AMPS

11.4

11.6

12.0

12.5

12.3

12.6

13.0

13.5

13.4

13.7

14.2

 

14.7

14.3

14.7

15.2

15.8

15.3

15.7

16.2

16.8

16.2

16.6

17.2

17.9

 

 

 

 

 

HI PR

231

248

262

274

259

279

294

307

295

317

335

 

349

335

361

381

398

377

406

429

447

417

449

474

494

 

 

 

 

 

LO PR

108

115

125

133

114

121

132

141

118

126

138

 

147

124

132

145

154

130

139

151

161

135

144

157

167

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MBh

47.5

48.4

50.7

54.1

46.4

47.3

49.5

52.8

45.3

46.1

48.3

 

51.6

44.2

45.0

47.1

50.3

42.0

42.8

44.8

47.8

38.9

39.6

41.5

44.3

 

 

 

 

 

S/T

0.98

0.95

0.86

0.70

1.00

0.98

0.89

0.72

1.00

1.00

0.91

 

0.74

1.00

1.00

0.94

0.76

1.00

1.00

0.98

0.79

1.00

1.00

0.98

0.80

 

 

 

 

1800

Delta T

24

23

22

19

24

24

22

19

23

24

22

 

19

23

23

23

20

21

22

22

19

20

20

21

18

 

 

 

 

KW

3.23

3.30

3.41

3.53

3.49

3.57

3.69

3.81

3.72

3.80

3.93

 

4.06

3.92

4.01

4.14

4.28

4.09

4.18

4.32

4.47

4.23

4.33

4.48

4.63

 

 

 

 

 

AMPS

11.9

12.2

12.6

13.1

12.9

13.2

13.7

14.2

14.0

14.4

14.9

 

15.5

15.0

15.4

15.9

16.6

16.0

16.4

17.0

17.7

17.0

17.4

18.0

18.8

 

 

 

 

 

HI PR

243

261

276

288

272

293

309

323

310

333

352

 

367

353

380

401

418

397

427

451

470

439

472

498

520

 

 

 

 

 

LO PR

113

121

132

140

120

128

139

148

125

133

145

 

154

131

139

152

162

137

146

159

170

142

151

165

175

 

 

 

 

 

MBh

46.1

47.0

49.2

52.5

45.0

45.9

48.1

51.3

43.9

44.8

46.9

 

50.1

42.9

43.7

45.8

48.8

40.7

41.5

43.5

46.4

37.7

38.5

40.3

43.0

 

 

 

 

 

S/T

0.94

0.91

0.82

0.66

0.97

0.94

0.85

0.69

1.00

0.96

0.87

 

0.71

1.00

0.99

0.90

0.73

1.00

1.00

0.93

0.76

1.00

1.00

0.94

0.76

 

 

85

 

1600

Delta T

25

24

23

20

25

25

23

20

25

25

23

 

20

25

25

24

20

23

24

23

20

22

22

22

19

 

 

 

KW

3.21

3.28

3.38

3.50

3.46

3.54

3.65

3.78

3.69

3.77

3.89

 

4.03

3.88

3.97

4.10

4.25

4.05

4.14

4.28

4.43

4.20

4.29

4.44

4.59

 

 

 

 

 

AMPS

11.8

12.1

12.5

13.0

12.8

13.1

13.5

14.1

13.9

14.3

14.8

 

15.3

14.9

15.3

15.8

16.4

15.9

16.3

16.8

17.5

16.9

17.3

17.9

18.6

 

 

 

 

 

HI PR

240

259

273

285

270

290

306

320

307

330

349

 

363

349

376

397

414

393

423

447

466

434

467

493

515

 

 

 

 

 

LO PR

112

120

130

139

119

126

138

147

123

131

143

 

153

130

138

150

160

136

144

158

168

140

149

163

174

 

 

 

 

 

MBh

42.5

43.4

45.4

48.5

41.5

42.4

44.4

47.3

40.6

41.3

43.3

 

46.2

39.6

40.3

42.2

45.1

37.6

38.3

40.1

42.8

34.8

35.5

37.2

39.7

 

 

 

 

 

S/T

0.91

0.87

0.79

0.64

0.94

0.91

0.82

0.66

0.96

0.93

0.84

 

0.68

0.99

0.96

0.86

0.70

1.00

0.99

0.90

0.73

1.00

1.00

0.91

0.73

 

 

 

 

1400

Delta T

25

25

24

20

26

25

24

21

26

25

24

 

21

26

25

24

21

25

25

24

20

23

23

22

19

 

 

 

 

KW

3.13

3.20

3.30

3.41

3.38

3.45

3.56

3.68

3.59

3.67

3.79

 

3.92

3.78

3.87

4.00

4.14

3.95

4.04

4.17

4.32

4.09

4.18

4.32

4.47

 

 

 

 

 

AMPS

11.5

11.7

12.1

12.6

12.4

12.7

13.2

13.7

13.5

13.9

14.3

 

14.9

14.5

14.8

15.3

15.9

15.4

15.8

16.4

17.0

16.4

16.8

17.4

18.0

 

 

 

 

 

HI PR

233

251

265

276

262

281

297

310

297

320

338

 

353

339

365

385

402

381

410

433

452

421

453

479

499

 

 

 

 

 

LO PR

109

116

127

135

115

122

134

142

120

127

139

 

148

126

134

146

155

132

140

153

163

136

145

158

169

 

23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Entering Indoor Dry Bulb Temperature

 

 

NOTE: Shaded area is AHRI Rating Conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOLING PERFORMANCE DATA

GSX130481A*

Page 23
Image 23
Goodman Mfg service manual GSX130481A, Model GSX13048-1AA / CA*F4860*6** / ZP39K5E-PFV, 46.0, 15.7, 149