CONDENSING UNIT SPECIFICATIONS |
|
| GSX130181A* | GSX130241A* | GSX130301A* | GSX130361A* |
|
|
|
|
|
Cooling Capacity, BTUH | 18,000 | 24,000 | 30,000 | 36,000 |
Compressor |
|
|
|
|
R.L. Amps | 9.00 | 13.4 | 12.8 | 16.6 |
L.R. Amps | 48.0 | 58.3 | 64.0 | 79.0 |
High Pressure Switch |
|
|
|
|
Open | 610 PSIG | 610 PSIG | 610 PSIG | 610 PSIG |
Close | 420 PSIG | 420 PSIG | 420 PSIG | 420 PSIG |
Condenser Fan Motor |
|
|
|
|
Horsepower | 1/6 | 1/6 | 1/6 | 1/6 |
F.L. Amps | 1.10 | 1.10 | 1.10 | 1.10 |
Liquid Line, Inches O.D.* | 3/8" | 3/8" | 3/8" | 3/8" |
Suction Line, Inches O.D.* | 3/4" | 3/4" | 3/4" | 3/4" |
Refrigerant Charge | 120.0 | 116.0 | 129.0 | 131.0 |
Power Supply |
| |||
Minimum Circuit Ampacity(1) | 12.3 | 17.9 | 17.1 | 21.9 |
Maximum Overcurrent Device(2) | 20 | 30 | 30 | 35 |
Electrical Conduit Size |
|
|
|
|
Power Supply (Inches) | 1/2 or 3/4 | 1/2 or 3/4 | 1/2 or 3/4 | 1/2 or 3/4 |
Approximate Shipping Weight | 178 | 178 | 180 | 197 |
| GSX130421A* | GSX130481A* | GSX130601A* |
|
|
|
|
Cooling Capacity, BTUH | 42,000 | 48,000 | 60,000 |
Compressor |
|
|
|
R.L. Amps | 17.9 | 19.8 | 26.4 |
L.R. Amps | 112.0 | 109.0 | 134.0 |
High Pressure Switch |
|
|
|
Open | 610 PSIG | 610 PSIG | 610 PSIG |
Close | 420 PSIG | 420 PSIG | 420 PSIG |
Condenser Fan Motor |
|
|
|
Horsepower | 1/6 | 1/4 | 1/4 |
F.L. Amps | 1.10 | 1.50 | 1.50 |
Liquid Line, Inches O.D.* | 3/8" | 3/8" | 3/8" |
Suction Line, Inches O.D.* | 7/8" | 7/8" | 7/8" |
Refrigerant Charge | 151.0 | 166.0 | 184.0 |
Power Supply | |||
Minimum Circuit Ampacity(1) | 23.5 | 26.3 | 34.5 |
Maximum Overcurrent Device(2) | 40 | 45 | 60 |
Electrical Conduit Size |
|
|
|
Power Supply (Inches) | 1/2 or 3/4 | 1/2 or 3/4 | 1/2 or 3/4 |
Approximate Shipping Weight | 219 | 225 | 240 |
(1)Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
(2)Maximum Overcurrent Protection Device: MUST use time delay fuses or
NOTES:
*Always check the S&R plate for electrical data on the unit being installed.
*Installer will need to supply 7/8" to 1 1/8" adapters for suction line connections.
*Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
*Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT NOT THE INDOOR COIL.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
6