Greenheck Fan GGH20 manual Sequence of Operation Grease Grabber H2O, Normal Fan Operation

Models: GGH20

1 28
Download 28 pages 42.5 Kb
Page 20
Image 20

Sequence of Operation - Grease Grabber™ H2O

WASH

Hot Water Recovery: (0 min.) Adjustable

Shut OFF exhaust fan(s)

Stage 1:

Fill hood tank (hot water)

Stage 2:

Wash primary filters

Detergent pump ON

Spray for 5 minutes

Stage 3:

Wash secondary filters

Detergent pump ON

Spray for 5 minutes

2 minute delay for water settling

Stage 4:

Wash primary filters

Detergent pump OFF

Spray for 5 minutes

Stage 5:

Wash secondary filters

Detergent pump OFF

Spray for 5 minutes

Stage 6:

Drain soapy/dirty water

Normal Fan Operation

RINSE

Stage 7:

Fill hood tank (hot water)

Stage 8: Rinse primary filters Detergent pump OFF

Spray for 5 minutes

Stage 9:

Rinse secondary filters Detergent pump OFF

Spray for 5 minutes

Stage 10:

Drain rinse water

DRY

Turn ON exhaust fan(s)

20 minute dry time

Turn OFF exhaust fan(s)

Wash, rinse & dry complete

Exhaust Mode in Fire -- RUN

Exhaust Mode in Fire -- STOP

Temperature Interlock

START FAN

Fan(s) will run

No

FIRE

Yes

Exhaust

Fan(s) remain

ON

START FAN

Fan(s) will run

No

FIRE

Yes

Exhaust Fan(s) will turn OFF

Fan(s) OFF

Temperature

>95°F.

(Adjustable)

Exhaust Fan(s) will turn ON

20 Model GGH2O

®

Page 20
Image 20
Greenheck Fan GGH20 manual Sequence of Operation Grease Grabber H2O, Normal Fan Operation