Airflow Testing Procedure

Short Ridge Meter Components

For measuring exhaust airflow rates (cubic feet per minute = CFM), use a short ridge meter to measure velocities along the inlet slot of the hood. To ensure accurate data, all appliances should be on. Multiple locations need to be tested as outlined below to ensure an accurate reading.

Hood Length

48 to 72

72 to 120

120 to 192

inches

inches

inches

 

 

 

 

 

Minimum Number

3

5

7

of Test Locations

 

 

 

 

 

 

 

To take velocity readings along the length of the hood, the edge of the short ridge meter must start/stop six

(6)inches from the end of the hood. Vertical placement of the short ridge meter along the inlet is shown.

After the appropriate number of readings have been taken from the inlet slot of the hood, an average reading can be calculated by summing the velocity readings and dividing the total value by the number of readings taken.

Sum of Velocity Readings

Average Velocity =

Number of Readings

Next calculate the total hood airflow volume (CFM) by using the following equation:

Hood CFM = [(Length of Hood in inches x 4.846) x (Average inlet slot velocity x 2.47)]  144

NOTE

The constants 4.846 and 2.47 are factory derived for use with the Grease Grabber™ H2O.

Calculation Example:

Five (5) inlet slot velocity readings (minimum)

Hood Length

96 inches

 

 

 

 

 

 

 

 

 

Test Location

6

27

48

69

90

(off left; in inches)

 

 

 

 

 

 

 

 

 

 

 

Velocity Reading (fpm)

175

210

250

190

160

 

 

 

 

 

 

Average Velocity (FPM) =

(175 + 210 + 250 + 190 + 160)  5 = 197 FPM

Hood Exhaust Rate (CFM) =

[(96 x 4.846) x (197 x 2.47)]  144 = 1572 CFM

®

Model GGH2O 21