4. Pipe the Optional Vent Line

4. Pipe the Optional Vent Line

If an optional vent line is located between the safety shutoff valves it must be piped to the outdoors.

warning

Reference the National Fuel Gas Code for additional vent line requirements.

 

Vent Line Solenoid

 

To Outdoors

 

Vent Line

To Burner

From Supply

Safety

Shut-off Valves

Optional Vent Line

5. Test the System for Leaks

Check both the supply lines and the factory piping for leaks. Apply a soap and water solution to all piping and watch for bubbling which indicates a leak.

warning

NEVER test for a gas leak with an open flame.

Note

The factory piping has been checked for leaks, but should be rechecked due to shipping and installation.