Vent Pipe Runs

All Power Vented water heaters generate a certain amount of operational noise. In order to minimize noise transmission to floor joists though hangers, place some soft material such as foam rubber, approximately 12mm (1/2 in.) thick, between hangers and the vent pipes.

1.

Horizontal runs must not, under any circumstances, run

 

downhill then run uphill thus forming a valley where con-

 

densation can accumulate and block the vent pipe.

2.

Horizontal runs require a minimum 3mm (1/8 in.) rise

 

per 1.5m (5 ft) and a support every 1.2m (4 ft.). Ensure

 

there is enough height between heater and termination

 

to raise vent pipe runs the required distance.

3.

Vertical runs require a support every 1.5m (5 ft.) that

 

must provide proper support to prevent stress on the

(a)

FOR 40 AND 50 GALLON HEATERS.

VENT PIPE

50mm (2 in.)

BLOWER ASS’Y WITH RUBBER COUPLING

TOP GEAR

FOR 50mm (2 in.) NOMINAL ABS OR CPVC

CLAMP

VENT PIPE.

 

PVC VENTING REQUIRES ADAPTOR KIT

RUBBER

COUPLING

P/N 73901 (SEE FIGURE 14).

BOTTOM

 

 

GEAR

 

CLAMP

 

BLOWER

 

OUTLET

 

FLANGE

 

BLOWER

pipes.

Vent Pipe Connection to Blower

A rubber coupling is supplied with the water heater to con- nect the venting to the blower using gear clamps (supplied). Important: These connections must be properly sealed to prevent the leakage of the products of combustion into the living area.

Rubber Coupling Connection

(b)

FOR 40 AND 50 GALLON HEATERS. BLOWER ASS’Y WITH RUBBER COUPLING FOR 76mm (3 in.) NOMINAL ABS OR CPVC VENT PIPE.

PVC VENTING REQUIRES ADAPTOR KIT P/N 73901 (SEE FIGURE 14).

VENT PIPE 76mm (3 in.)

REDUCER

76mm - 50mm

(3 in. - 2 in.)

ABS and CPVC vent piping may be directly connected to the blower assembly as shown in Figures 15 & 16. For heaters installed as shown in Figure 15 (c), order 50mm (3 in.) rub- ber coupling connector (P/N 63234).

PVC vent pipe installations must use a PCV vent conversion kit as shown in Figure 14. Order PVC Vent Conversion Kit P/N 73901 for 50mm (2 in.) vent pipe installations. For 76mm (3 in.) vent pipe installations order PVC Vent Conversion Kit P/N 73876.

1.

Clean and lightly sand the end of the vent pipe that will

 

connect to the rubber coupling. This will ensure a good

 

mechanical connection between the coupling and the

 

pipe.

2.

Apply solvent cement and join the PVC coupling of the

 

adaptor to the venting system. (PVC Only).

3.

At the rubber coupling, loosen the upper gear clamp to

 

allow the vent piping to be inserted fully 32mm (1-1/4

(c)

FOR 40 AND 50 GALLON HEATERS. BLOWER ASS’Y WITH RUBBER COUPLING FOR 76mm (3 in.) NOMINAL ABS OR CPVC VENT PIPE.

PVC VENTING REQUIRES ADAPTOR KIT P/N 73876 (SEE FIGURE 14).

VENT PIPE 76mm (3 in.)

RUBBER

COUPLING

P/N 63234

in.) deep. Do not use sealant or glue.

Figure 15 Blower, Fittings and Vent Pipe Options

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PVC PIPE

 

 

 

 

 

 

 

 

 

COUPLING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

76mm (3 in.)

 

 

MODEL 5065 HEATERS. BLOWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50mm (2 in.)

 

 

 

 

 

 

 

 

 

 

ADAPTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

ASS’Y WITH RUBBER COUPLING FOR

 

ADAPTOR

 

 

 

 

 

 

 

 

 

 

FOR PVC

 

 

 

 

 

 

 

 

 

 

 

 

 

76mm (3 in.) NOMINAL ABS, CPVC OR

 

FOR PVC

 

 

 

 

 

 

 

 

 

 

(P/N 73876)

 

 

 

 

 

 

 

 

 

 

 

 

 

PVC VENT PIPE.

 

(P/N 73901)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIPE

 

 

 

 

 

 

 

 

 

 

(CPVC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPPER GEAR

 

 

 

 

 

 

 

 

 

CLAMP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RUBBER

 

 

 

 

 

 

 

 

 

 

ADAPTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOWER

 

 

 

 

 

 

 

 

GEAR CLAMP

 

 

 

 

 

Figure 14 Pipe Assembly Adaptors

 

 

 

Figure 16 Blower, Fittings and Vent Pipe Options

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 14
Image 14
GSW 5065 manual Vent Pipe Runs, Vent Pipe Connection to Blower, Rubber Coupling Connection