SECTION 3.2

PART 3

V-TYPE PREPACKAGED

OPERATIONAL ANALYSIS

TRANSFER SWITCHES

 

 

 

 

 

 

 

UTILITY RESTORED, TRANSFER SWITCH DE-ENERGIZED

After the preset time interval expires the circuit board will open the Wire 23 circuit to ground. The transfer relay de-energizes, it’s normally closed contacts close, and utility source voltage is delivered to the utility closing coil (C1), via Wires N1A and N2A, closed Transfer Relay Contacts 1 and 7, and Limit Switch XA1.

Figure 7. Utility Restored, Transfer Relay De-energized.

Page 3.2-7

Page 57
Image 57
Guardian Technologies 4760 Utility RESTORED, Transfer Switch DE-ENERGIZED, Utility Restored, Transfer Relay De-energized