V-TYPE PREPACKAGED TRANSFER SWITCHES

PART 3

SECTION 3.4

DIAGNOSTIC TESTS

a.Connect the negative meter lead to the ground lug. INFINITY should be measured.

b.Connect the negative meter lead to Wire 23 at ICT or terminal strip. INFINITY should be measured.

c.Connect the negative meter lead to Wire 194 at ICT or terminal strip. INFINITY should be measured.

d.Connect the negative meter lead to the neutral connection. INFINITY should be measured.

6.Set your VOM to the 'R x 1" scale. Connect the positive meter test lead to wire N2.

a.Connect the negative meter lead to the ground lug. INFINITY should be measured.

b.Connect the negative meter lead to Wire 23 at ICT or terminal strip. INFINITY should be measured.

c.Connect the negative meter lead to Wire No. 194 at ICT or terminal strip. INFINITY should be measured.

d.Connect the negative meter lead to the neutral connection. INFINITY should be measured.

7.Disconnect wire N1 and wire N2 from transformer TX.

8.Connect one test lead to wire N1 removed in step 7, and the other test lead to the ground terminal. INFINITY should be measured.

9.Connect one test lead to wire N2 removed in step 7, and the other test lead to the ground terminal. INFINITY should be measured.

10.If no short is indicated in steps 5 through 9, proceed with steps 11 through 15. If a short is indicated in steps 5 through 9, repair shorted wiring.

11.Reconnect wires N1 and N2 to the interconnection terminal or terminal strip.

12.Replace fuses F1 and F2 in the fuse holder.

13.Turn on the utility power supply to the transfer switch using whatever means is provided.

14.Set VOM to measure AC voltage. Connect one test lead to wire N1 and the other test lead to wire N2. Utility line to line voltage should be measured.

15.Turn off the utility power supply to the transfer switch using whatever means is provided.

RESULTS:

If a short is indicated in steps 5 through 9, repair wiring and re-test. If utility line to line voltage is measured in Step 14, proceed to Test 35.

TEST 35 - CHECK TRANSFORMER (TX)

DISCUSSION:

The transformer is a step down type and has two functions. It supplies approximately 16VAC to the control board for utility sensing. It also supplies approximately 16 VAC to the battery charger when utility is available for trickle charge. A shorted transformer can result in fuse F1 or F2 blowing.

PROCEDURE:

1.On the generator panel, set the AUTO-OFF-MANUAL switch to OFF.

2.Turn off the utility power supply to the transfer switch, using whatever means is provided.

3.See Figure 6. Disconnect Wires N1, N2, 224, 225, 224A, 225A from transformer (TX).

4.Set a VOM to the "R x 1" scale.

5.Connect one test lead to TX terminal 1. Connect the other test lead to TX terminal 5. Approximately 38.5 ohms should be measured

6.Connect one test lead to TX terminal 10. Connect the other test lead to TX terminal 9. Approximately 1.5 ohms should be measured.

7.Connect one test lead tot TX terminal 7. Connect the other test lead to TX terminal 6. Approximately 0.3 ohms should be measured.

8.Connect one test lead to TX terminal 1. Connect the other test lead to the transformer case. INFINITY should be measured.

9.Connect one test lead to TX terminal 7. Connect the other test lead to the transformer case. INFINITY should be measured.

10.Connect one test lead to TX terminal 9. Connect the other test lead to the transformer case. INFINITY should be measured.

11.Connect one test lead to TX terminal 1. Connect the other test lead to TX terminal 10. INFINITY should be measured.

Page 3.4-9

Page 70
Image 70
Guardian Technologies 4759, 4456, 4390, 4389, 4760, 4758 manual Test 35 Check Transformer TX