PART 3
SECTION 3.4
DIAGNOSTIC TESTS
6.Set the generator main line circuit breaker to its "On" or "Closed" position.
7.Set the generator
a.The generator should crank and start.
b.About 15 seconds after engine startup, the transfer relay should energize and transfer to the ’Standby" source should occur.
8.When you are certain that transfer to "Standby" has occurred, turn ON the utility power supply to the transfer switch. After a 15 seconds, retransfer back to the "Utility" source should occur.
9.Locate on the utility closing coil the terminal that Wire A is connected to (see Figure 1, Page
other meter test lead to this terminal. Generator line to line voltage should be indicated. If generator voltage is NOT indicated, proceed to Step 10.
10.With Wire N2A still connected to one test probe, connect the other meter test lead to Wire 126 on Limit Switch XA1 (see Figure 1, Page
RESULTS:
1.In Step 7, if the generator does NOT crank or start, refer to Part 4, "DC Control".
2.In Step 7, if transfer to the "Standby" source does NOT occur, go to Problem 1.
3.In Step 9, if normal utility source
4.If normal utility source
5.If normal utility source
TEST 30 - CHECK FUSES F1 AND F2
DISCUSSION:
Fuses F1 and F2 are connected in series with the Utility 1 and Utility 2 circuits, respectively. A blown fuse will open the applicable circuit and will result in
(a)generator startup and transfer to "Standby", or (b) failure to retransfer back to the UTILITY source.
Figure 5. Fuse Holder and Fuses
PROCEDURE:
1.On the generator panel, set the
2.Turn off the utility power supply to the transfer switch, using whatever means provided.
3.Remove fuses F1 and F2 from the fuse holder (see Figure 5).
4.Inspect and test fuses for blown condition.
RESULTS:
1.Replace blown fuse(s) and proceed to Test 34.
2.For Problem 7 (DC Control section), go to Test 27.
TEST 31 - TEST LIMIT SWITCH XA1
DISCUSSION:
When the transfer switch main contacts are actuated to their "Utility" position, limit switch XA1 should be mechanically actuated to its open position. On transfer to the "Standby" position, the limit switch should actuate to its closed position. If the switch does not actuate to its closed position, retransfer back to "Utility" will not occur.
PROCEDURE:
1.With the standby generator shut down, set its AUTO-
2.Turn OFF the utility power supply to the transfer switch, using whatever means provided.
Page