Service Settings, Cont.

Display

Meaning

Possible Values

Comments

Total

 

Total number of regenerations since

Cannot be reset

 

Regens

00000

Service Settings was last entered

00000–99999

 

Total

 

Total amount of water that has

Cannot be reset

 

Gallons

00000000

passed through the appliance since

00000000–99999999

 

 

 

Service Settings was last entered

 

 

Mode 1

 

Operating (Regeneration) Mode

Mode 1

See Operating Modes

Frequency

 

 

Frequency

section that follows

 

 

 

Mode 1

 

 

 

 

Days of the Week

 

 

 

 

Mode 2

 

 

 

 

Demand Delayed

 

 

 

 

Mode 3

 

 

 

 

Demand

 

Days

 

Number of days between

00 to 12

Displays only when in

Between Regenerations 01

regenerations

 

Mode 1

 

 

 

 

Frequency

Regen

SMTWTFS

Select which days to regenerate

Various combinations or Y’s

Displays only when in

Days

YYYYYYYY

 

and blank spaces

Mode 1

 

 

 

 

Days of the Week

Hardness

 

Hardness of the water that was

003 to 999 Grains

This is the actual hardness

Grains

040

tested

(00000 to 99999 mg/L)

reading and is not

 

 

 

 

compensated for iron

Iron

 

Amount of iron in parts per million of

00 to 99 ppm (mg/L)

This value is used to

ppm

00

the water that was tested

 

calculate compensated

 

 

 

 

hardness automatically

Manganese

 

Amount of manganese in parts per

00 to 99 ppm (mg/L)

This value is used to

ppm

00

million of incoming water

 

calculate compensated

 

 

 

 

hardness automatically

Salt Type

 

Regenerant filling the brine tank

Sodium

 

Sodium

 

 

Potassium

 

Compensated

 

Compensated hardness using the

Cannot be set

The formula used is:

Hardness

00040

hardness, iron, and manganese

ppm or (mg/L)

Hardness + (4 x each ppm

 

 

settings

 

iron) + (4 x each ppm

 

 

 

 

manganese) =

 

 

 

 

compensated hardness

Capacity

 

The desired capacity number

00000 to 99999 Grains

 

Grains

28730

 

(0000 to 9999 gm)

 

WaterMax 60 Series Owner’s Manual

11/10/2008

16