Installation Procedure

3. PREPARATION FOR THE INSTALLATION

(1) Position of ceiling opening between unit and suspending bolt.

Indoor unit 570mm

Ceiling opening 650mm

Ornament panel 700mm

Distance between

 

 

suspending bolts 535mm

 

 

Indoor unit 570mm

 

 

Ceiling opening 650mm

 

 

Ornament panel 700mm

 

 

(For series 142, 182 )

Overlap between ceiling and ornament panel shall be 25mm

Suspending bolts

 

 

150mm

320mm

Ceiling

Ornament panel

60mm

 

 

 

 

 

 

 

 

(For series 242, 282 )

950(Ornament panel)

890(Ceiling opening)

840(Indoor unit)

 

Refrigerant pipe

780

Suspending bolts

(Distancesuspendingbetweenbolts)

A (Distance between suspending bolts)

840(Indoor unit)

890(Ceiling opening)

950(Ornament panel)

A

Suspending bracket

(For series 362, 422, 482, 602 ) 060710**

1280(Ceiling opening)

1270 (Distance between suspending bolts)

515

060608**

suspending bolts)

opening)

780 (Distance between

860(Ceiling

515

 

Note:

Dimension of ceiling opening marked with * can be as large as 910mm, but the matching part of ceiling with ornament panel shall be over 20mm.

(160)

CeilingA

(2)Cut an opening in ceiling for installation if necessary. (when ceiling already exists.) Refer to paper pattern for dimension of ceiling hole.

20 Over

Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation.

Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration. Contact your real estate dealer

(3) Install a suspending bolt. (Use a M10 bolt)

To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new ceiling, use built-in type bolt or parts prepared in the field.

Before going on installing adjust space between ceiling.

<Installation example>

50~100

Roof

Anchor bolt

Long nut

Suspending bolt

Ceiling

Note: All the above mentioned parts shall be prepared in field.

21

Page 23
Image 23
Haier AB142ACERA, AB422ACERA, AB142ACEAA operation manual Preparation for the Installation, Installation example