Connection of pipe

Installation procedure

Connection of pipe

1.Connection of pipe Connection method

1.Connection of pipe Connection method For the specific max length and the max fall of connection pipe, please refer to the manual of outdoor unit.

3. The additional charging amount of refrigerant In order to guarantee the efficiency, the pipe should be as short as possible.

4.Vacuumizing Daub the refrigerant oil on the joint and the flared nut.

5.Leakage detection When bending the pipes, give the roundness as large as possible, to avoid crashing the pipes.

6.Thermal insulation treatment To connect the pipe, fit the center and use hand to screw the nut, then use s-

panner to tighten the nut, as shown in figure.

Pay attention not to let alien matters,

Joint Nut

such as sand, vapor get into the pipe.

 

The connection of indoor unit pipe

Spanner

must be performed by using two

spanners.

Spanner

2. Dimension of connection pipe

 

Pipe diameter

Fasten torque

Liquid pipe 9.52mm

32.7~39.9 N.m

Gas pipe 19.05mm

97.2~118.6 N.m

If do not fit the center and screw the nut hard, the screw thread may be damaged, which will cause refrigerant leakage.

3. The additional charging amount of refrigerant

Manual backgroundThe additional charging of refrigerant (R407C) should be complied with the installation manual of outdoor unit. It must use measurer to quantificationally charge. The additional charging amount must be complied with the specified amount.

Requirements: Both excessive charging and less charging of refrigerant will cause the compressor trouble. It must be complied with the specified amount.

4.Vacuumizing

Manual background Use vacuum pump to perform vacuumizing through the stop valve of outdoor unit.

Manual backgroundIt is strictly prohibited to use the refrigerant sealed in the outdoor unit to perform air discharging.

5.Leakage detection

Manual background Use leakage detector or soap water to check if the connected part of the connection pipe and the valve cap leak.

6.Thermal insulation treatment

Manual background The thermal insulation of connection pipe should be performed at both gas side and liquid side. In COOLING, both liquid side and gas side are in low temperature, in order to prevent dew from forming, thermal insulation should be done.

Manual background The thermal insulation material at the gas side must use the material with the heat resistant temperature over 120*.

Manual background The connected part of indoor unit connection pipe should be thermal insulated.