Haier HC42D2VAR, HC36D2VAR, HC30D2VAR, HC24D2VAR, HC18D2VAR operation manual and vapor pressures

Models: HC18D2VAR HC24D2VAR HC30D2VAR HC36D2VAR HC42D2VAR

1 17
Download 17 pages 27.1 Kb
Page 15
Image 15

Symptom

Possible Cause

Remedy

 

Power off or loose electrical connection

Make sure main switch is ON. Check and tighten all connections.

 

Incorrect thermostat setting

Set thermostat correctly

No cooling

Defective contactor

Check for 24V at contactor coil.

 

Open circuit breaker of blown fuses

Reset or replace

 

Defective transformer

Check wiring - Replace it.

 

Interconnecting low voltage wiring damage

Replace thermostat wiring

 

Dirty filters

Clean & replace

 

Indoor air blockage

Check supply registers and return grills for blockage.

 

Blocked outdoor coil

Clear away leaves and other debris

 

Improperly sized unit

Recalculate load

Insufficient Cooling

Improper airflow

Check - should be 400CFM/Ton

 

Incorrect refrigerant charge

Charge correctly per instruction.

 

Air, non-condensibles or moisture in system

Recover refrigerant, evacuate & recharge, add filter drier

 

Incorrect voltage

At compressor terminals, voltage must be within

 

 

10% of rating plate volts when unit is running.

Water on floor or in

 

 

furnace

Blocked condensate drain and "P" trap

Remove blockage

 

 

 

 

Run or start capacitor defective

Replace

 

Loose connection

Check and tighten all connections.

Condenser fan runs,

Compressor stuck, grounded or open

Wait for 2 hours for overload to reset.

compressor doesn't

motor winding, open internal overload

Replace compressor if still open.

 

Low voltage condition

At compressor terminals, voltage must be within 10% of rating

 

 

plate volts when unit is running.

 

Low voltage condition

Add start kit components

 

Incorrect voltage

At compressor terminals, voltage must be within 10% of rating

Compressor

 

plate volts when unit is running.

short-cycling

Defective overload protector

Replace - check for correct voltage

 

Refrigerant undercharge

Add refrigerant

Register sweat

Low evaporator airflow

Increase blower speed or reduce restriction - replace air filter

 

Restriction in liquid line,

Replace defective components

High head - Low

metering device or filter drier

 

vapor pressures

Flowrator piston size too small

Change to correct size piston

 

Incorrect capillary tubes

Change coil assembly

 

Blocked outdoor coil

Clear away leaves and other debris

High head - High

Refrigerant overcharge

Correct system charge

or normal vapor

Condenser fan not running

Repair or replace

pressures

Air, non-condensibles or

Recover refrigerant, evacuate &

 

moisture in system

recharge, add filter drier

Low head - High

Flowrator piston size too large

Change to correct size piston

vapor pressures

Defective compressor valves

Replace compressor

 

Incorrect capillary tubes

Replace coil assembly

Low vapor - cool

Low evaporator airflow

Increase blower speed or reduce restriction - replace air filter

compressor - iced

Operating below 65 F outdoors

Add low ambient kit

evaporator coil

Moisture in the system

Recover refrigerant, evacuate & recharge, add filter drier

High vapor

Excessive load

Recheck load calculation

pressure

Defective compressor

Replace

Fluctuating head

Air or non-condensibles in system

Recover refrigerant, evacuate & recharge.

and vapor pressures

 

 

Pulsing noise at

Air or non-condensibles in system

Recover refrigerant, evacuate & recharge

metering device

 

 

or liquid line

 

 

 

 

 

13

Page 15
Image 15
Haier HC42D2VAR, HC36D2VAR, HC30D2VAR, HC24D2VAR, HC18D2VAR operation manual and vapor pressures