Fine Tuning Draft

With fire burning and stablized take draft reading in flue pipe and note the reading. Next take a reading in the fire box by removing the bolt in the front center of the unit.

While watching the draft meter, close the restricter plate on the combus- tion blower slowly, until the needle reads about the same as it did on the flue. An example would be a flue read- ing of .05 and a firebox reading of .02. Close the restricter plate until the firebox reading is .04 to.05. Closing the restricter plate will reduce the positive pressure from the blower and increase the negative pressure in the firebox.

WARNING!

If draft is at .00, carbon monoxide will escape into the room. Too much carbon monoxide can kill you.

10

Timer settings shown above will perform well in most cases.

Verti-Flow Stoker Control

This section describes the features and opera- tions of The Harman Verti-Flow Stoker Control. The timers are adjustable from 0 minutes to 15 minutes in 1 minute steps. There are red lights on the front panel to show proper operation of the timer. One indicator shows power is applied to the unit. The other 3 indicators show when power is available at the adjacent receptacle.

The stoker control will be mounted on the side panel of the feeder directly below the coal hopper. The three receptacles and switch will be facing forward. The power cord, 3 AMP fuse access port and the thermostat connections to the rear.

The top receptacle provides power to the coal feeder motor. Thus, the plug from the coal feeder motor should be inserted into this receptacle.

The center receptacle provides power for the combustion blower motor. Thus, the plug from the combustion blower should be inserted into this receptacle.

The bottom receptacle provides power for the distribution blower motor. Thus, this final receptacle should be connected to the plug from the distribution blower motor.

Restricter Plate

DO NOT BURN WET COAL