Front |
Top View | 9 |
|
18" |
barometric |
damper |
34" |
34"
8"
16"
8"
minimum 4"
IMPORTANT
Use onlyU.L. approved board
Clearance to Combustibles
draft adjustment
IMPORTANT
Take draft readingbetween the barometric damperandthe stove.Do this onpilot mode.
INSTALLATION
Place the stoker a minimum of 4" to a com- bustible wall from the rear of the hopper and a minimum of 34" from the sides. The stove should be placed on a noncombustible floor. Install a 6" stove pipe from flue opening to chimney with a barometric damper. Secure all pipe joints with sheet metal screws. Plug power cord into a 120 volt receptacle.
Refer to the section on operation to light a fire. With the stove burning and stabilized set barometric damper at .04 to .06 on the draft meter. We do not expect you to own a draft meter. There- fore, have your dealer do
If your chimney will not produce .04 on the draft meter, a draft inducer should be installed by your dealer. The draft inducer will provide the additional draft needed for proper operation.
DO NOT BURN WET COAL