2. Top Vent - Vertical Termination

No Elbow

12 ft (3.66 m) min.

60 ft (18.29 m) max.

Figure 7.7

Two Elbows

12 ft (3.66 m) min.

60 ft (18.29 m) max.

Maximum horizontal run is 100% of vertical, but cannot exceed 26 ft (7.92 m)

Figure 7.8

Note: If installing a vertical vent/ termination off the top of the appli- ance, the vertical termination baffle should be used.

Note: If installing a vertical vent/ termination off the top of the appli- ance, the vertical termination baffle should be used.

Heatilator • Caliber CD Series • 4040-263 Rev N • 11/08