6 Termination Locations

A. Vent Termination Minimum Clearances

WARNING

Fire Risk.

Maintain vent clearance to combustibles as specified.

DO NOT pack air space with insulation or other materials.

Failure to keep insulation or other materials away from vent pipe may cause overheating and fire.

 

 

Horizontal

 

 

overhang

24 in. min.

20 in.

 

(508 mm)

 

(610 mm)

Vertical

Lowest

 

wall

 

Discharge

 

Termination

Opening

 

 

 

Cap

 

 

Storm Collar

 

X

 

12

 

 

Roof

 

 

Flashing

 

Roof Pitch

 

 

is X / 12

H (min.) - Minimum height from roof to lowest discharge opening.

Roof Pitch

H (Min.) Ft.

Roof Pitch

H (Min.) Ft.

Flat to 6/12

 

1.0*

Over 11/12 to 12/12

4.0

Over 6/12 to 7/12

1.25*

Over 12/12 to 14/12

5.0

Over 7/12 to 8/12

1.5*

Over 14/12 to 16/12

6.0

Over 8/12 to 9/12

2.0*

Over 16/12 to 18/12

7.0

Over 9/12 to 10/12

2.5

Over 18/12 to 20/12

7.5

Over 10/12 to 11/12

3.25

Over 20/12 to 21/12

8.0

 

* 3 ft. minimum in snow regions

 

 

Direct Vent Gas, Wood or Fuel

Oil Termination

20 in.

 

 

A

(508 mm)

18 in.

 

(minimum) to

 

 

Perpendicular

(457 mm)

 

 

Wall

 

B

 

(DV only)

 

 

 

Gas

 

 

 

Termination

 

 

 

Termination Caps Staggered Height

A

Gas Termination

Wood or Fuel Oil Termination

B

6 in. (152 mm) min.

20 in. (508 mm) min.

Figure 6.2 Staggered Termination Caps

Direct Vent Gas, Wood or Fuel

Oil Termination

Wood, Gas or

 

 

 

 

 

 

 

Fuel Oil

 

 

 

 

20 in.

 

 

Termination

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(508 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(minimum) to

 

 

 

 

20 in. min. *

 

 

 

Perpendicular

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wall

 

 

 

 

 

 

(508 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(DV only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Termination Caps Same Height

*If using decorative cap cover(s), this distance may need to be increased. Refer to the installation instruc- tions supplied with the decorative cap cover.

Figure 6.3 Leveled Termination Caps

Figure 6.1 Minimum Height From Roof To Lowest Discharge Opening

20

Heatilator • Caliber Mesh CD Series-SIT Valve • 4040-849 Rev J • 06/08