Hearth and Home Technologies CD4236MIR Vent Diagrams, Top Vent Horizontal Termination, One Elbow

Models: CD4236MR CD4842MLR CD4236MLR CD4236MIR CD4236MILR CD4842MILR CD4842MIR CD4842MR

1 76
Download 76 pages 3.36 Kb
Page 23
Image 23

E. Vent Diagrams

To replace the first starter elbow with two 45° elbows, refer to Figure 7.4. All other 90° elbows can be replaced with two 45° elbows.

General Rules:

SUBTRACT 3 ft. from the total H measurement for each 90° elbow installed horizontally.

SUBTRACT 1-1/2 ft. from the total H measurement for each 45° elbow installed horizontally.

A maximum of three 90° elbows (or six 45° elbows) may be used in any vent configuration. Some elbows may be installed horizontally. See Figure 7.9.

Elbows may be placed back to back anywhere in the system as long as the first 90° elbow is a starter elbow except as shown in Figure 7.4.

When penetrating a combustible wall, a wall shield firestop must be installed.

When penetrating a combustible ceiling, a ceiling firestop must be installed.

Horizontal runs of vent do not require vertical rise; horizontal runs may be level.

1. Top Vent - Horizontal Termination

One Elbow

V1

H1

V1 min.

V1 max.

H1 max.

ft

m

ft

m

ft

m

0

0.00

-

-

1.5

0.46

0.5

0.15

-

-

6

1.83

 

 

 

 

 

 

1

0.30

-

-

11

3.35

1.5

0.46

-

-

18

5.49

2

0.61

-

-

25

7.62

 

 

 

 

 

 

 

DVP

25

7.62

25

7.62

 

SLP

23

7.01

23

7.01

You may install a DVP elbow directly on top of the CD4236M. The CD4842M requires the DVP6 vent section prior to the elbow.

Figure 7.3

Note: The CD series appliances can adapt to SLP series vent pipe when venting off the top of the appliance. You must use a DVP-SLP24 adapter which can only be attached to the appliance starting collar.

When looking at horizontal termination diagrams, the adapter is not counted as part of the minimum vertical (V1 min.) requirements.

Whether horizontal or vertical termination, the adapter is counted as part of the maximum vertical limitations.

All venting rules for the vent run must still be followed.

HORIZONTAL EXAMPLE

V1 = 1 ft.

H1 = 11 ft. max.

DVP

V1 = 1 ft.

H1 = 11 ft.

max

DVP-SLP24

SLP

VERTICAL EXAMPLE

 

 

 

 

DVP-SLP24

12 ft (3.66 m) min.

12 ft (3.66 m) min.

Adapter

60 ft (18.29 m) max.

60 ft (18.29 m) max.

 

DVP

SLP

Heatilator • Caliber Mesh CD Series-SIT Valve • 4040-849 Rev J • 06/08

23

Page 23
Image 23
Hearth and Home Technologies CD4236MIR, CD4842MR, CD4842MIR Vent Diagrams, Top Vent Horizontal Termination, One Elbow