F. Vent Diagrams

1.Top Vent - Horizontal Termination One Elbow

Note: Use SLP Series components only.

WARNING**

Fire Risk.

When using SLP-HRC-SS and SLP-HRC-ZC-SS termination caps on top vented fireplaces, a one foot minimum vertical vent section is required

before installing first elbow.

When using DVP-TB1 termination cap on top vented fireplaces, a three foot minimum vertical vent section is required before installing first elbow.

V1 Minimum**

H1 Maximum

90 Elbow Only**

2 ft.

610 mm

 

 

 

 

1/2 ft.**

152 mm

2 ft.

610 mm

 

 

 

 

1-1/2 ft.**

457 mm

3 ft.

914 mm

2-1/2 ft.**

762 mm

5 ft.

1.5 m

3-1/2 ft.

1.1 m

7 ft.

2.1 m

 

 

 

 

4-1/2 ft.

1.4 m

15 ft.

4.6 m

H1 MAX. =15 ft. (4.6 m)

V1 + H1 MAX. = 40 ft. (12.2 m)

** See Warning.

H1

Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 7.3).

V1

Figure 7.4

24

Hearth & Home Technologies • DV3732SBI, DV3732SBIL • 2215-900 Rev. F • 9/12

Page 24
Image 24
Hearth and Home Technologies DV3732SBIL manual Vent Diagrams Top Vent Horizontal Termination One Elbow, Fire Risk