1. Top Vent - Horizontal Termination - (continued)

Two Elbows

Note: Use SLP Series components only.

Note: There MUST be a 25% re- duction in total H when using flex vent except when using the sim- ple up and out installation (see Figure 7.3).

V1 Minimum**

H1 + H2 Maximum

90 Elbow Only**

1/2 ft.

152 mm

 

 

 

 

1/2 ft.**

152 mm

1 ft.

305 mm

1-1/2 ft.**

457 mm

2 ft.

610 mm

2-1/2 ft.**

762 mm

4 ft.

1.2 m

 

 

 

 

3-1/2 ft.

1.1 m

6 ft.

1.8 m

 

 

 

 

4-1/2 ft.

1.4 m

14 ft.

4.3 m

H1 + H2 MAX. =14 ft. (4.3 m)

V1 + H1 + H2 MAX. = 40 ft. (12.2 m)

**See Warning Below.

H2

INSTALLED

HORIZONTALLY

WARNING**

Fire Risk.

When using SLP-HRC-SS and SLP-HRC-ZC-SS termination caps on top vented fireplaces, a one foot minimum vertical vent section is required before installing first elbow.

When using DVP-TB1 termination cap on top vented fireplaces, a three foot minimum vertical vent section is required before installing first elbow.

H1

V1

Figure 7.5

Hearth & Home Technologies • DV3732SBI, DV3732SBIL • 2215-900 Rev. F • 9/12

25

Page 25
Image 25
Hearth and Home Technologies DV3732SBIL manual Top Vent Horizontal Termination Two Elbows, Installed Horizontally