2. Top Vent - Vertical Termination - (continued)
Two Elbows
V2
H1
Note: Use SLP Series components only.
Figure 7.9
Three Elbows
V2
V1
V1 Minimum | H1 Maximum | ||
90 Elbow Only | 457 mm | ||
|
|
|
|
1/2 ft. | 152 mm | 2 ft. | 610 mm |
457 mm | 3 ft. | 914 mm | |
762 mm | 5 ft. | 1.5 m | |
|
|
|
|
1.1 m | 7 ft. | 2.1 m | |
|
|
|
|
1.4 m | 15 ft. | 4.6 m |
H1 MAX. =15 ft. (4.6 m)
V1 + V2 + H1 MAX. = 40 ft. (12.2 m)
Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 7.3).
V1 Minimum | H1 + H2 Maximum | ||
90 Elbow Only | 1/2 ft. | 152 mm | |
1/2 ft. | 152 mm | 1 ft. | 305 mm |
457 mm | 2 ft. | 610 mm | |
|
|
|
|
762 mm | 4 ft. | 1.2 m | |
|
|
|
|
1.1 m | 6 ft. | 1.8 m | |
1.4 m | 14 ft. | 4.3 m |
H1 + H2 MAX. =14 ft. (4.3 m)
V1 + V2 + H1 + H2 MAX. = 40 ft. (12.2 m)
Note: Use SLP Series components only.
H2
Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 7.3).
H1
INSTALLED
HORIZONTALLY
V1
Figure 7.10
28 | Hearth & Home Technologies • DV3732SBI, DV3732SBIL • |