Hearth and Home Technologies PIER-HVB-CE Ceiling Firestop Ceiling Side, Trapezoid Termination Cap

Models: PIER-HVB-CE ST-HVB-CE LCOR-HVB-CE RCOR-HVB-CE

1 44
Download 44 pages 19.18 Kb
Page 29
Image 29

If the area above the ceiling is NOT an attic, position and secure the ceiling firestop on the ceiling side of the previously cut and framed hole.

JOIST

CEILING

NAILS (4 REQUIRED)

CEILING FIRESTOP

Figure 22. Ceiling Firestop (Ceiling Side)

If the area above the ceiling IS an attic, position and secure the firestop on top of the previously framed hole.

NOTE: Keep insulation away from the flue pipe at least 25mm.

NOTE: There must be NO INSULATION or other combustibles inside the framed firestop opening.

 

NAILS (4 REQUIRED)

 

RAFTER

CEILING

 

 

CEILING FIRESTOP

Figure 23.

Attic Firestop

C. Flue Termination

For Horizontal Terminations - To attach and secure the termination to the last section of horizontal flue refer to the Cinch Pipe and Termination Cap installation instructions.

Push on and snap lock as described at the beginning of the Installing Flue Components section.

The termination kit should pass through the wall firestops from the exterior of the building.

Adjust the termination cap to its final exterior position on the building and interlock the flue sections.

WARNING: THE TERMINATION CAP MUST BE

!POSITIONED SO THAT THE ARROW IS POINTING UP.

For trapezoidal cap termination kits:

Using screws secure the cap to the exterior wall through the flanges in the cap.

!WARNING: FLUEING TERMINALS SHALL NOT BE RECESSED INTO A WALL OR SID-

ING. FLUE TERMINATION CLEARANCES MUST BE FOLLOWED TO AVOID FIRE DANGER.

7 1/4" (184mm)

Figure 24. Trapezoid Termination Cap

Heat & Glo • PIER/ST/L&RCOR-HVB-CE2068-900 Rev. H • 6/07

29

Page 29
Image 29
Hearth and Home Technologies PIER-HVB-CE, RCOR-HVB-CE, LCOR-HVB-CE Ceiling Firestop Ceiling Side, Trapezoid Termination Cap