Step 6. The Gas Supply Line
NOTE: Have the gas supply line installed in accordance with local building codes by a qualified installer approved and/or licensed as required by the locality.
NOTE: Before the first firing of the fireplace, the gas supply line should be purged of any trapped air.
NOTE: Consult local building regulations to properly size the gas supply line leading to the (Rp 1/2 in.)
This threaded gas inlet connection is ISO
To install the gas supply line:
•Locate the gas line access hole in the outer casing of the fireplace.
•The gas line may be run from either side of the fireplace provided the hole in the outer wrap does not exceed 51mm (2 in.) in diameter and it does not penetrate the actual firebox.
•Open the fireplace lower grille, insert the gas supply line through the gas line hole, and connect it to the
•When attaching the pipe, support the control so that the lines are not bent or torn.
•After the gas line installation is complete, all connec- tions must be tightened and checked for leaks with a
!WARNING: DO NOT USE AN OPEN FLAME TO CHECK FOR GAS LEAKS.
Table 1
•Insert insulation from the outside of the fireplace and pack the insulation tightly to totally seal between the pipe and the outer casing.
•At the gas line access hole the gap between the supply piping and gas access hole can be plugged with non- combustible insulation to prevent cold air infiltration.
USE A WRENCH ON
WHEN TIGHTENING
GAS LINE.
MANUAL
VALVE
FLEX CONNECTOR
GAS VALVE
GAS LINE | CONTROL VALVE |
ACCESS |
Figure 29. Gas Supply Line
Step 7. Gas Pressure Requirements
Pressure requirements for Heat & Glo gas fireplaces are shown in Table 1 below.
A tap is provided on the outlet side of the gas control for a test gauge connection to measure the manifold pressure. To measure inlet pressure, provisions must be made to attach a test gauge to the tap immediately upstream of the gas supply connection to the fireplace.
The fireplace and its individual
If the fireplace must be isolated from the gas supply piping system by closing an individual
| Natural Gas | Propane | Butane | Natural Gas |
| (G20) | (G31) | (G30) | (G25) |
______________________________________________________________ |
| |||
Inlet Pressure | 20mbar | 37 or 50mbar | 30 or 50mbar | 25mbar |
Manifold Pressure | ||||
Gas Rate | .54 m3/h | .24 m3/h | .16 m3/h | .54 m3/ |
|
|
|
| h |
Max.Input(NETCV) | 9.6 kW | 9.9 kW | 7.9kW | 7.8 kW |
|
|
|
|
|
Burner Injector | DMS 33 | DMS 51 | DMS 53 | DMS 33 |
|
|
|
|
|
Pilot Injector | 51 | 30 | 30 | 51 |
|
|
|
|
|
Heat & Glo • | 33 |