M
N
P
R
Q
See Notes 3 & 4
V
(See Note 2)
V
T
S Electrical S
Service
D*
V
V
V
= VENT TERMINAL | X = AIR SUPPLY INLET |
= AREA WHERE TERMINAL IS NOT PERMITTED
A | = | 31 cm | clearances above grade, veranda, | K |
| = | 1.8 M |
| clearance to a mechanical | ||||||
|
| (See Note 1) | porch, deck or balcony |
|
|
|
|
|
|
|
| (powered) air supply inlet | |||
|
| L** |
| = | 2.1 M |
| clearance above paved | ||||||||
B | = | 31 cm | clearances to window or door |
|
| ||||||||||
|
|
|
| (See Note 1) |
|
| sidewalk or a paved driveway | ||||||||
|
|
| that may be opened, or to perma- |
|
|
|
|
|
|
|
| located on public property | |||
|
|
| nently closed window. (Glass) | M*** = | 46 cm |
| clearance under veranda, porch, | ||||||||
D* | = | 31 cm | vertical clearance to unventilated |
|
|
|
|
|
|
|
| deck, balcony or overhang | |||
|
|
|
| 1.1 M |
| vinyl | |||||||||
|
|
| soffit or to ventilated soffit located |
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| above the terminal | S | = | 15 cm | clearance from sides of elec- | ||||||||
|
| 76 cm | for vinyl clad soffits and below |
|
|
|
| (See Note 5) |
| trical service | |||||
|
| T | = | 31 cm | clearance above electrical | ||||||||||
|
|
| electrical service | ||||||||||||
F | = | 23 cm | clearance to outside corner |
|
|
|
| (See Note 5) |
| service | |||||
|
|
|
|
|
|
|
|
|
|
|
| ||||
G | = | 15 cm | clearance to inside corner |
| Alcove Applications |
|
|
|
|
| |||||
|
|
|
|
|
| ||||||||||
| N |
| = | 15 cm |
|
| |||||||||
|
|
|
|
|
|
|
| ||||||||
H | = | 91 cm | not to be installed above a gas |
|
|
|
| 31 cm |
| vinyl sidewalls |
| ||||
|
|
| meter/regulator assembly within 90 |
| P |
| = | 2.4 M |
|
|
|
|
|
| |
|
|
| cm horizontally from the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| of the regulator |
|
|
|
|
|
| QMIN |
| RMAX |
|
| |
I | = | 1.8 M | clearance to gas service regulator |
|
| 1 cap |
| .91 M |
| 2 x Q ACTUAL |
|
| |||
|
| 2 caps |
| 1.8 M |
| 1 x Q ACTUAL |
|
| |||||||
|
|
| vent outlet |
|
|
|
|
|
| ||||||
|
|
|
|
| 3 caps |
| 2.7 M |
| 2/3 x Q ACTUAL |
|
| ||||
J | = | 31 cm | clearance to |
|
|
|
|
|
| ||||||
|
| 4 caps |
| 3.7 M |
| 1/2 x Q ACTUAL |
|
| |||||||
|
|
| air supply inlet to building or the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| combustion air inlet to any other |
| QMIN = # termination caps x 3 RMAX = (2 / # termination caps) x QACTUAL |
|
| ||||||||
|
|
| gas stove |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
**a flue shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
***only permitted if veranda, porch, deck or balcony is fully open on a minimum of 2 sides beneath the floor, or meets Note 2.
NOTE 1: On private property where termination is less than 7 feet above a sidewalk, driveway, deck, porch, veranda or balcony, use of a listed cap shield is suggested. (See flue components page)
NOTE 2: Termination in an alcove space (spaces open only on one side and with an overhang) are permitted with the dimensions specified for vinyl or
Figure 4.4 Minimum Clearances for Termination
NOTE 3: Local codes or regulations may require different clearances.
NOTE 4: Termination caps may be hot. Consider their proximity to doors or other traffic areas.
NOTE 5: Location of the flue termination must not interfere with access to the electrical service.
Heat & Glo assumes no responsibility for the improper performance of the gas stove when the flueing system does not meet these requirements.