B. Install Fireplace & Chimney
Install as per Sections 7 and 8.
C. Install Chase Top Flashing
•You MUST use a chase top flashing in a chase installation. Chase top flashings are available from your Heat & Glo dealer or may be field constructed.
For chase enclosures, use a chase top flashing. The chase top flashing allows for a 1 1/2 in. (38 mm) clearance around the outside of the chimney pipe for ventilation air. Install the chase top flashing at the top of the chase with a 1/2 in. (13
mm)air clearance off the top of the chase constructions (Figure 9.4, 9.5). Use spacing clips to ensure the 1/2 in.
(13 mm) air clearance. If the chase top flashing does not fit the dimensions of the chase, a custom flashing can be
|
| Storm collar must |
|
1/2 in. air space | be installed 1 in. |
| |
off chase top |
| ||
established by |
| ||
| Chase Top | ||
spacers |
| ||
|
|
| Flashing |
1/2 in. |
|
| |
Air Space |
|
| |
| (Not furnished by | 1/2 | |
|
| ||
|
| ||
| Spaces Locally |
| |
¨ Figure 9.4 | Chase Top Construction |
|
1 | 1/2 |
|
Figure 9.5 Chase Top Construction
6 in. Min.
Figure 9.6 Chase Top Construction
D. Install Termination Cap
Install the chimney sections up through the chase enclo- sure.
•Install termination caps following instructions provided with them.
WARNING! Risk of Fire! The minimum overlap of cap to pipe (as shown in the following illustrations) MUST be met or chimney may separate from cap. Separation al- lows sparks, heat and embers to escape.
NOTICE: Paint the termination cap with a
Heat & Glo • | 31 |