Heat & Glo LifeStyle 50 owner manual B. Clearances

Models: 50

1 52
Download 52 pages 55.52 Kb
Page 18
Image 18
B. Clearances

B. Clearances

WARNING! Risk of Fire! You must comply with all minimum air space clearances to combustibles as specified in Fig- ure 6.2. DO NOT pack required air spaces with insulation or other materials.

Storm Collar

Roof Flashing

(attic)

(insulation)

2 in. (51 mm) min. Manual backgroundManual background

Shaded areas

represent

Manual background 2 in. (51 mm) min. air space clearance required around pipe

Attic

Insulation

Shield

(ceiling)

Offset/Return (secured

with hanger straps)

(ceiling)

Ceiling Firestop Manual background

Object

 

Combustible

48 in.

 

 

1219 mm

 

0 in.

 

to floor

 

 

Must have 2 in. (51 mm)

minimum clearance

to header

Manual background 0 in. to level of standoffs

Manual background 1-1/2 in. (38 mm) to back & sides of appliance

(except at nailing flanges where it is 1/2 in. [13 mm])

Figure 6.2 Air Space Clearances

18

Heat & Glo • RUTHERFORD-504059-333 Rev C • 06/08

Page 18
Image 18